Toshiba Q9+ Installation & Operation Manual page 111

Adjustable speed drives
Table of Contents

Advertisement

V/f 5-Point Setting Frequency 1
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 1 setting establishes the fre-
quency that is to be associated with the voltage setting of
(V/f 5-Point Setting Voltage 1).
The V/f 5-Point settings define a volts-per-hertz relationship for
the start up output of the ASD.
To enable this function, set the V/f Pattern
V/f 5-Point Curve setting.
V/f Curves may be useful in starting high inertia loads such as
rotary drum vacuum filters.
https://www.toshiba.com/tic/
F190
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
(F015)
selection to the
F191
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
F191
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
F190
99