Virtual Linear Pump Application Operating Mode
Program Virtual Linear Pump Settings
While operating in the Virtual Linear Pump mode, this parameter
sets the system response to the received feedback from the V/I
terminal.
Select Direct Acting to produce an increase in the ASD output
with a decrease in the feedback signal.
Select Reverse Acting to produce a decrease in the ASD output
with an decrease in the feedback signal.
Settings:
0 — Direct Acting (Positive Gradient)
1 — Reverse Acting (Negative Gradient)
Virtual Linear Pump Sleep Timer
Program Virtual Linear Pump Sleep Timer
During a properly configured Virtual Linear Pump operation, this
parameter Enables/Disables the ability of the ASD to terminate
the output signal to the motor upon operating for a user-set
amount of time within the
old)
threshold.
and
See
F383
F480
for additional information on this parameter.
WARNING
The Sleep Timer function may result in the unexpected
Start or Stop of the motor. Signs to this effect are to be
posted at the location of the motor/pump.
Settings:
0 — Disabled
1 — Enabled
Virtual Linear Pump Sleep Delay Timer
Program Virtual Linear Pump Sleep Timer
During a properly configured Virtual Linear Pump operation, and
once enabled at F382, this parameter establishes the time that
system operation will be allowed to operate within the
ear Pump Minimum (Threshold)
to the motor is terminated.
See
F382
for additional information on this parameter.
https://www.toshiba.com/tic/
F380
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Virtual Linear Pump Minimum (Thresh-
threshold before the ASD output
F385
Direct Access Number —
Parameter Type — Selection List
Factory Default — Direct Acting
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 300
Changeable During Run — Yes
Virtual Lin-
Minimum — 1
Maximum — 65535
Units — Seconds