Deceleration Time 1
Program Fundamental Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the
ASD to go from the Maximum Frequency to 0.0 Hz for the Decel-
eration 1 profile. The Accel/Decel Pattern may be set using F502.
Note: A deceleration time shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings
may lengthen the deceleration times.
Maximum Frequency
Program Fundamental Frequency Settings
This setting determines the absolute maximum frequency that the
ASD can output.
Accel/Decel times are calculated based on the Maximum Fre-
quency setting.
The Maximum Frequency is not limited by this setting while oper-
ating in the Drooping Control mode (see F320).
Note: This setting may not be lower than the Upper-Limit
Frequency (
F012)
Upper-Limit Frequency
Program Fundamental Frequency Settings
This parameter sets the highest frequency that the ASD will
accept as a frequency command or frequency setpoint. The ASD
may output frequencies higher than the Upper-Limit Frequency
(but, lower than the Maximum Frequency) when operating in the
PID Control mode, Torque Control mode, or the Vector Control
modes (sensorless or feedback).
Note: This setting may not be higher than the Maximum
Frequency
(F011 )
setting (F013).
Lower-Limit Frequency
Program Fundamental Frequency Settings
This parameter sets the lowest frequency that the ASD will
accept as a frequency command or frequency setpoint. The ASD
will output frequencies lower than the Lower-Limit Frequency
when accelerating to the lower limit or decelerating to a stop. Fre-
quencies below the Lower Limit may also be output when operat-
ing in the PID Control mode, Torque Control mode, or the Vector
Control modes (sensorless or feedback).
Note: This setting may not be higher than the Upper Limit
Frequency
(F012 )
78
F010
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
setting
.
setting or lower than the Lower Limit
setting.
F014
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 80.00
Changeable During Run — No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 66.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
https://www.toshiba.com/tic/