Toshiba Q9+ Installation & Operation Manual page 195

Adjustable speed drives
Table of Contents

Advertisement

Retain Trip Record at Power Down
Program Protection Trip Settings
This parameter Enables/Disables the Trip Record Retention set-
ting. When enabled, this feature logs the trip event and retains
the trip information when the system powers down. The trip infor-
mation may be viewed from the (Program  Utilities Trip His-
tory screen or the Monitor screen.
When disabled, the trip information will be cleared when the sys-
tem powers down.
Settings:
0 — Disabled
1 — Enabled
Emergency Off Mode
Program Protection Emergency Off Settings
This parameter determines the method used to stop the motor in
the event that an Emergency Off command is received and the
system is configured to use this feature.
This setting may also be associated with the FL terminals to allow
the FL relay to change states when an EOFF condition occurs by
setting the FL terminal to Fault FL (all) at F132.
Note: A supplemental emergency stopping system should be
used with the ASD. Emergency stopping should not be a
task of the ASD alone.
Settings:
0 — Coast Stop
1 — Deceleration Stop
2 — DC Injection Braking Stop
Emergency DC Braking Control Time
Program Protection Emergency Off Settings
When DC Injection is selected at
mines the time that the DC Injection Braking is applied to the
motor.
https://www.toshiba.com/tic/
F602
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F603
this parameter deter-
F605
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Selection List
Factory Default — Coast Stop
Changeable During Run — No
Direct Access Number —
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 20.0
Units — Seconds
F602
F603
F604
183