Process Increasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may increase for a given difference in the speed reference and
the PID feedback value.
Process Decreasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may decrease for a given difference in the speed reference and
the PID feedback value.
Frequency Command Detection Range
Program Feedback Feedback Settings
While operating in the PID mode, this parameter reads the feed-
back frequency. Once the feedback frequency is within the set-
ting of this parameter (F374) relative to the commanded
frequency, a properly configured output terminal is activated.
Available output terminal settings for this parameter include: FC =
RR, FC = RX, and FC = VI (see
FC is the frequency command and RR, RX, and VI are the input
terminals of the received feedback.
Number of PG Input Pulses
Program Feedback PG Settings
This parameter is used to set the number of pulses output from a
shaft-mounted encoder that is used to indicate one revolution of
rotation (360°) of the motor or of the motor-driven equipment.
Number of PG Input Phases
Program Feedback PG Settings
This parameter determines the type of information that is sup-
plied by the phase encoder.
Settings:
1 — Single Phase
2 — Two Phase
3 — Two Phase (Polarity Inversion)
https://www.toshiba.com/tic/
F372
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Table 12 on page
257), where
F377
Direct Access Number —
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Direct Access Number —
Parameter Type — Selection List
Factory Default — Two Phase
Changeable During Run — No
F372
F373
F374
F375
F376
149