Commercial Power/ASD Switching Frequency
Program Terminal Line Power Switching
When enabled at
F354 and with a properly configured discrete
output
terminal, this parameter sets the frequency at which the At
Frequency Powerline Switching function engages.
The At Frequency Powerline Switching function commands the
system to discontinue using the output of the ASD and to switch
to commercial power once reaching the frequency set here.
See
F354
for additional information on this parameter.
ASD Side-Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will
wait before outputting a signal to the motor once the switch-to-
ASD-output criteria has been met.
See
F354
for additional information on this parameter.
Commercial Power Side Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will
wait before allowing commercial power to be applied to the motor
once the switch-to-commercial-power criteria has been met.
See
F354
for additional information on this parameter.
Commercial Power Switching Freq. Hold Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the connec-
tion to commercial power is maintained once the switch-to-ASD-
output criteria has been met.
See
F354
for additional information on this parameter.
https://www.toshiba.com/tic/
F355
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F359
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.62
Changeable During Run — Yes
Minimum — 0.40
Maximum — 10.00
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
F355
F356
F357
F358
145