Command and Frequency Mode Control

Command control includes instructions such as Stop, Run, Jog, etc. The source of the Command
signal must be established for normal operation.
Frequency commands control the output speed of the ASD. The source of the frequency control signal
must be established for normal operation.
The source of the command control and frequency control may be either internal or external. Once the
source signal is selected for either function, the system may be configured to use the selected signal all
of the time or switch under user-defined conditions.
Command and Frequency control may be carried out using any one of several control methods (signal
sources) or combinations thereof. In the event that multiple control commands are received, the signal
sources are assigned priority levels. The primary control method for Command and Frequency control
uses the settings of

Command Control (F003)

The Command Mode selection of
primary source of the command input for the ASD.
However, the Override feature may supersede the
setting as indicated in
Table 5 on pg. 49
sources managed by the Override function. The level
of the control item of the hierarchy is listed from left to
right, most to least, respectively. As indicated in the table, the Override setting may supersede the
setting.
Placing the EOI in the Local mode selects the RS485 2-Wire as the Command Mode control source.
Local mode operation may be superseded by other Override settings.
Example: With the EOI set to Local, Communication Board input or RS485 4-Wire input will
supersede EOI control input.
The remaining control sources may be placed into the Override mode using communications.
The source of the Command control signal may be selected by:
• The
F003
setting,
• Placing an item from the Command signal source selections in the Override mode via
communications, or
• Placing the EOI in the Local mode (places only the RS485 [2-Wire] or the RS485 [4-Wire] in the
Override mode).
Possible Command signal source selections include the following:
• Terminal Board (default),
• EOI Keypad,
• RS485,
• Communication Option Board, or
F003
setting (is used if no signal sources are in the Override mode).
Note:
The Terminal Board is placed in the Override mode for Command functions by
assigning a discrete terminal to Command Terminal Board Priority and activating
the terminal by applying 120 VAC. Once activated (Run command required), the
Terminal Board settings will be used for Override Command control (F, R, Preset
Speeds, etc.).
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F003
and F004, respectively.
F003
establishes the
Table
5.
shows the hierarchy of the control
Standard Mode Selection
(F003) Command Mode
F003
Selection
Terminal Block
01:06
F003
47