Toshiba TOSVERT VF-PS1 series Instruction Manual

Toshiba TOSVERT VF-PS1 series Instruction Manual

Metasys n2 option unit
Hide thumbs Also See for TOSVERT VF-PS1 series:

Advertisement

TOSVERT
Metasys
N2 option unit Instruction Manual
®
1. Make sure that this instruction manual is delivered to the end use r of Metasys ®
N2 option unit.
2. Read this manual before installing or operating the Metasys ® N2 optio n unit.
Keep it in a safe place for reference.
3. All information contained in this manual are subject to change without notice.
Please confirm the latest information on our web site "www.inverter.co.jp".
VF-PS1
series
MTS001Z
NOTICE
E6581539

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TOSVERT VF-PS1 series

  • Page 1 E6581539 TOSVERT VF-PS1 series Metasys N2 option unit Instruction Manual ® MTS001Z NOTICE 1. Make sure that this instruction manual is delivered to the end use r of Metasys ® N2 option unit. 2. Read this manual before installing or operating the Metasys ® N2 optio n unit. Keep it in a safe place for reference.
  • Page 2 E6581539 Safety precautions On the inverter and in its instruction manual, important information is contained for preventing injuries to users, damages to assets, and for proper use of the device. Read the instruction manual attached to the inverter along with this instruction manual to completely understand the safety precautions, the symbols and indications shown below.
  • Page 3 E6581539 Limitation of use Safety precaution Never use this unit with any device other than TOSVERT VF-PS1 series inverters. Doing so may cause an accident. Handling in general Danger Never disassemble, modify or repair the product. Disassembling the product may cause electric shocks, fire or injuries.
  • Page 4 E6581539 Wiring Warning Electrical construction work must be done by a qualified expert. Connection of input power by someone who does not have expert knowledge may result in electric shocks or fire. Turn off input power before wiring. Mandatory Wait at least minutes and make sure that the charge lamp (on the inverter unit) is no longer lit.
  • Page 5 E6581539 Preface ® Thank you for purchasing the “ Metasys N2 option (MTS001Z)” for TOSVERT VF-PS1 inverter. By Installing this board into the VF-PS1, data communication can be made with a host computer or ® other device via Metasys N2 network. Before using this unit, carefully read this instruction manual in order to completely and correctly ®...
  • Page 6: Table Of Contents

    E6581539 Table of Contents 1. Overview ···································································································································6 2. Names and functions·················································································································6 2.1. Outline·······························································································································6 ® 2.2. Metasys N2 Connector····································································································6 2.3. LED indicator·····················································································································7 3. Installing the MTS001Z ·············································································································8 3.1. Network cable connection ·································································································9 3.2. Network configuration········································································································9 4. Parameters······························································································································10 4.1. Communication parameters ····························································································10 4.2.
  • Page 7: Overview

    E6581539 1. Overview The Metasys ® N2 interface (MTS001Z) allows the VF-PS1 inverter to be connected into a Metasys ® N2 network. 2. Names and functions The drawing below shows names and functions of main parts. 2.1. Outline Connector to the inverter Don’t use these connector or switches ®...
  • Page 8: Led Indicator

    E6581539 2.3. LED indicator The LED shows the present status of the network and error. Layout of LED The option has two LEDs. Those function are below table. (Green) (Red) State LEDs Comment COM LED: OFF ® Metasys N2 failure. ERR LED: Flashing 5 times in 1 sec COM LED: OFF Communication loss detected.
  • Page 9: Installing The Mts001Z

    E6581539 Installing the MTS001Z Install the Metasys ® N2 option to VF-PS1 as follows. Please install this option (MTS001Z) on the top of options when you install two options. Do not install under the another option. (1) Turn off input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on...
  • Page 10: Network Cable Connection

    E6581539 3.1. Network cable connection ® Connect the Metasys N2 network cable to communication option as follows. Title Description Wire type Shielded twisted cable Characteristic impedance Between 100 and 130 ohm Distributed impedance between Less than 100pF per meter conductors Distributed impedance between Less than 200pF per meter conductors and shield...
  • Page 11: Parameters

    E6581539 4. Parameters 4.1. Communication parameters Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set to correct value, this unit can not work normally. Title Function Description 0: No action Network Time-Out 0000 ...
  • Page 12: F851 : Operation At Communication Error By Disconnection

    E6581539 4.3. : Operation at communication error by disconnection f851 This parameter sets up the VF-PS1 response to a loss of communications with the ® Metasys N2 network. 0: Stop and Communication release The inverter decelerates the motor to a stop and gives an  alarm (the leftmost LED ...
  • Page 13: The Metasys ® N2 Local/Remote Operation

    E6581539 5. The Metasys N2 Local/Remote Operation ® The example below shows how to configure the VF-PS1 for local/remote operation. F terminal....Operating command ® R terminal ....The Metasys N2 local/remote (Terminal in this example) switching RR/S4 terminal ..Operation frequency command <Wiring>...
  • Page 14: Specifications

    E6581539 6. Specifications < Environmental specification > Item Specification Model number MTS001Z Indoors, an altitude of 3000m or less, where the product will not be exposed to direct sunlight, corrosive or explosive gasses, vapor, Service environment coarse particulate including dust, and where there is no grinding or grinding oil nearby.