ACC Precision Air Conditioner Controller
User Manual
Table 3-4 Modbus TCP parameter settings
Parameter
Connection
mode
Client
encryption
Server
encryption
EMS IP
address
EMS port
----End

3.2.6 Setting Communications Parameters (SNMP Settings)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
displayed.
Issue 02 (2016-11-30)
Setting
Server, Client,
Server+client
Enable, Disable
Enable, Disable
N/A
N/A
To set communications parameters, log in as the Admin or Engineer user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a precision
air conditioner to an EMS (element management system).
One precision air conditioner supports concurrent access of up to 10 EMSs through
SNMP.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Setting Method
If you set Connection mode to Server, the air
conditioner, as a server, supports one client
connection and establishes communication.
If you set Connection mode to Client, the air
conditioner, as a client, can connect to a remote
server and establish communication.
If you set Connection mode to Server+client, the
air conditioner, as a server, supports one client
connection and establishes communication. In
addition, the air conditioner, as a client, can connect
to a remote server and establish communication.
The default value is Enable. This parameter is
configurable when Connection mode is set to Client.
The default value is Disable. This parameter is
configurable when Connection mode is set to Server.
Enter the actual IP address of the EMS. IP addresses of
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when
Connection mode is set to Client.
It is recommended that you retain the default value
16100. If you need to change the value, enter a value as
required. This parameter is configurable when
Connection mode is set to Client.
3 Power-on Commissioning
Figure 3-7
is
14