7.2 Motion Command Details
7.2.3 Zero Point Return (ZRET)
Parameters to be Set
Parameter
OW03,
Bits 0 to 3
OW05, Bit B
OL10
OW18
OW3C
OL3E
OL40
OL42
7-54
Name
Select the setting unit for OL10 (Speed Reference Setting), OL3E
(Approach Speed), and OL40 (Creep Rate).
0: Reference unit/s
Speed Unit Selection
1: 10
2: Percentage of rated speed (1 = 0.01%)
3: Percentage of rated speed (1 = 0.0001%)
Zero Point Return Input
This signal must be turned ON by using the ladder program.
Signal
Set the positioning speed to use after detecting a phase-C pulse. The sign is
ignored.
Speed Reference
The travel direction will depend on the sign of the Zero Point Return Travel
Setting
Distance.
Setting to 0 or a negative value will result in an error.
This parameter allows the travel speed to be changed without changing the
Speed Reference Setting (OL10). The setting can be changed during
Override
operation.
Setting range: 0 to 32767 (0 to 327.67%)
Setting unit: 1 = 0.01%
Zero Point Return
18: INPUT & Phase-C Pulse Method
Method
Set the speed to be used at zero point return start.
Approach Speed
The travel direction depends on the sign of the approach speed.
Setting to 0 will result in an error.
Set the speed and travel direction (sign) after the INPUT signal is detected.
Creep Rate
Setting to 0 will result in an error.
Zero Point Return Travel
Set the travel distance from the point where a phase-C pulse is detected.
Distance
The travel direction will depend on the sign.
Setting
n
reference units/min