Data storage in LCP
1.
Go to 0-50 LCP Copy
2.
Press the [OK] key
3.
Select "All to LCP"
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
NOTE!
Stop the motor before performing this operation.
Connect the LCP to another Adjustable frequency drive
and copy the parameter settings to this Adjustable
frequency drive as well.
Data transfer from LCP to Adjustable frequency drive
1.
Go to 0-50 LCP Copy
2.
Press the [OK] key
3.
Select "All from LCP"
4.
Press the [OK] key
The parameter settings stored in the LCP are now
transferred to the Adjustable frequency drive indicated by
the progress bar. When 100% is reached, press [OK].
NOTE!
Stop the motor before performing this operation.
®
VLT
HVAC Drive Programming Guide
Alarm
Main
Log
Menu
Auto
Reset
on
MG11CD22 - VLT
®
is a registered Danfoss trademark
2.1.4 Parameter Set-up
The Adjustable frequency drive can be used for practically
all assignments, thus offering a significant number of
parameters. The series offers a choice between two
programming modes - the Quick Menu mode and the
Main Menu mode.
The latter provides access to all parameters. The former
takes the user through a few parameters making it
possible to program the majority of VLT
applications.
Regardless of the mode of programming, parameters can
be changed in both Quick Menu mode and in Main Menu
mode.

2.1.5 Quick Menu Mode

Parameter Data
The graphical display (GLCP) provides access to all
parameters listed under the quick menus. The numeric
display (NLCP) only provides access to the quick set-up
parameters. To set parameters using the [Quick Menu]
button, enter or change parameter data or settings in
accordance with the following procedure:
1.
Press the Quick Menu button
2.
Use the [
] and [
] buttons to find the parameter
you want to change
3.
Press [OK]
4.
Use [
] and [
] buttons to select the correct
parameter setting
5.
Press [OK]
6.
To move to a different digit within a parameter
setting, use the [
] and [
7.
Highlighted area indicates digit selected for
change
8.
Press [Cancel] button to disregard change, or
press [OK] to accept change and enter the new
setting
Example of changing parameter data
Assume 22-60 Broken Belt Function is set to [Off]. However,
you want to monitor the fan-belt condition - non- broken
or broken - according to the following procedure
1.
Press Quick Menu key
2.
Choose Function Setups with the [
3.
Press [OK]
4.
Choose Application Settings with the [
5.
Press [OK]
®
HVAC Drive
] buttons
] button
] button
2-7