Parameter Description
1-93 Thermistor Source
Option:
Function:
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] or [2] cannot be
selected if the analog input is already in
use as a reference source (selected in
3-15 Reference 1 Source, 3-16 Reference 2
Source or 3-17 Reference 3 Source ).
When using MCB 112, choice [0] None
must always be selected.
[0]
None
*
[1]
Analog input 53
[2]
Analog input 54
[3]
Digital input 18
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
NOTE!
This parameter cannot be adjusted while the motor is
running.
NOTE!
Digital input should be set to [0] PNP - Active at 24 V in
5-00 Digital I/O Mode.
®
VLT
HVAC Drive Programming Guide
MG11CD22 - VLT
®
is a registered Danfoss trademark
3
3
3-27