Parameter Description
23-50 Energy Log Resolution
Option:
3
3
[0]
Hour of Day
[1]
Day of
Week
[2]
Day of
Month
[5]
Last 24
*
Hours
[6]
Last 7 Days
[7]
Last 5
Weeks
NOTE!
The Adjustable frequency drive has no backup of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power-down unless a Real Time
Clock module with backup is installed. Consequently the
logging will be stopped until date/time is readjusted in
0-70 Date and Time. In 0-79 Clock Fault it is possible to
program for a warning in case the clock has not been set
properly, e.g., after a power-down.
23-51 Period Start
Range:
Size related
*
NOTE!
When mounting an Analog I/O MCB 109 option card, a
battery backup of the date and time is included.
3-150
®
VLT
Function:
Select the desired type of period for logging
of consumption. Hour of Day [0], Day of
Week [1] or Day of Month [2]. The counters
contain the logging data from the
programmed date/time for start (23-51 Period
Start) and the numbers of hours/days as
programmed for (23-50 Energy Log Resolution).
The logging will start on the date
programmed in 23-51 Period Start, and
continue until one day/week/month has
gone. Last 24 Hours [5], Last 7 Days [6] or
Last 5 Weeks [7]. The counters contain data
for one day, one week or five weeks back in
time and up to the current time.
The logging will start at the date
programmed in 23-51 Period Start. In all cases,
the period split will refer to Operating Hours
(time where Adjustable frequency drive is
powered up).
Function:
[ 0 - 0 ]
MG11CD22 - VLT
HVAC Drive Programming Guide
23-53 Energy Log
Range:
0
[0 -
4294967295 ]
*
NOTE!
All counters are automatically reset when changing the
setting in 23-50 Energy Log Resolution. At overflow the
update of the counters will stop at maximum value.
NOTE!
When mounting an Analog I/O MCB 109 option card, a
battery backup of the date and time is included.
23-54 Reset Energy Log
Option:
[0] Do not reset
[1] Do reset
®
is a registered Danfoss trademark
Function:
Array with a number of elements equal to the
number of counters ([00]-[xx] below
parameter number in display). Press OK and
Step between elements by means of
buttons on the Local Control Panel.
Array elements:
Figure 3.63
Data from latest period is stored in the
counter with the highest index.
At power-down, all counter values are stored
and resumed at next power-up.
Function:
Select Do reset [1] to reset all values in the
Energy Log counters shown in 23-53 Energy
Log. After pressing OK, the setting of the
parameter value will automatically change to
Do not reset [0].