Parameter Description
16-65 Analog Output 42 [mA]
Range:
Function:
0.000
[0.000 -
View the actual value at output 42 in
*
30.000 ]
mA. The value shown reflects the
selection in 6-50 Terminal 42 Output.
16-66 Digital Output [bin]
Range:
Function:
0
[0 - 15 ]
View the binary value of all digital outputs.
*
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual frequency rate on terminal
*
29.
16-68 Pulse Input #33 [Hz]
Range:
Function:
0
[0 - 130000 ] View the actual value of the frequency
*
applied at terminal 33 as an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of impulses applied to
*
terminal 27 in digital output mode.
16-70 Pulse Output #29 [Hz]
Range:
Function:
0
[0 - 40000 ] View the actual value of pulses to terminal 29
*
in digital output mode.
16-71 Relay Output [bin]
Range:
Function:
0
[0 - 511 ]
View the settings of all relays.
*
Figure 3.45
16-72 Counter A
Range:
Function:
0
[-2147483648 -
View the present value of Counter A.
*
2147483647 ]
Counters are useful as comparator
operands, see 13-10 Comparator Operand.
®
VLT
HVAC Drive Programming Guide
16-72 Counter A
Range:
16-73 Counter B
Range:
0
16-75 Analog In X30/11
Range:
0.000
16-76 Analog In X30/12
Range:
0.000
16-77 Analog Out X30/8 [mA]
Range:
0.000
3.16.5 16-8* Serial communication bus &
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range:
0
MG11CD22 - VLT
®
is a registered Danfoss trademark
Function:
The value can be reset or changed either
via digital inputs (parameter group 5-1*)
or by using an SLC action (13-52 SL
Controller Action).
Function:
[-2147483648 -
View the present value of Counter B.
*
2147483647 ]
Counters are useful as comparator
operands (13-10 Comparator Operand).
The value can be reset or changed either
via digital inputs (parameter group 5-1*)
or by using an SLC action (13-52 SL
Controller Action).
Function:
[-20.000 - 20.000 ] View the actual value at input
*
X30/11 of MCB 101.
Function:
[-20.000 - 20.000 ] View the actual value at input
*
X30/12 of MCB 101.
Function:
[0.000 - 30.000 ] View the actual value at input X30/8
*
in mA.
FC Port
Function:
[0 -
View the two-byte control word (CTW) received
*
65535 ]
from the bus master. Interpretation of the
control word depends on the Serial
communication bus option installed and the
control word profile selected in 8-10 Control
Profile.
For more information, please refer to the
relevant Serial communication bus manual.