Danfoss VLT FC 100 Series Programming Manual page 33

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

Parameter Description
0-20 Display Line 1.1 Small
Option:
[1602]
Reference %
*
3
3
[1603]
Status Word
[1605]
Main Actual Value
[%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor voltage
[1613]
Frequency
[1614]
Motor Current
[1615]
Frequency [%]
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Motor Thermal
[1622]
Torque [%]
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link Voltage
3-6
®
VLT
HVAC Drive Programming Guide
Function:
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in percent.
Present status word
View the two-byte word sent with
the status word to the bus master
reporting the Main Actual Value.
View the user-defined readouts as
defined in 0-30 Custom Readout
Unit, 0-31 Custom Readout Min Value
and 0-32 Custom Readout Max Value.
Actual power consumed by the
motor in kW.
Actual power consumed by the
motor in HP.
Voltage supplied to the motor.
Motor frequency, i.e., the output
frequency from the adjustable
frequency drive in Hz.
Phase current of the motor
measured as effective value.
Motor frequency, i.e., the output
frequency from the adjustable
frequency drive in percent.
Present motor load as a percentage
of the rated motor torque.
Motor speed reference. Actual
speed will depend on slip compen-
sation being used (compensation
set in 1-62 Slip Compensation). If not
used, actual speed will be the value
read in the display minus motor
slip.
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
Shows the actual torque produced,
in percentage.
Intermediate circuit voltage in the
adjustable frequency drive.
MG11CD22 - VLT
®
0-20 Display Line 1.1 Small
Option:
[1632]
Brake Energy /s
[1633]
Brake Energy /2
min
[1634]
Heatsink Temp.
[1635]
Inverter Thermal
[1636]
Inv. Nom. Current
[1637]
Inv. Max. Current
[1638]
SL Controller
State
[1639]
Control Card
Temp.
[1643]
Timed Actions
Status
[1650]
External Reference Sum of the external reference as a
[1652]
Feedback [Unit]
[1653]
Digi Pot
Reference
[1654]
Feedback 1 [Unit]
[1655]
Feedback 2 [Unit]
[1656]
Feedback 3 [Unit]
[1658]
PID Output [%]
[1660]
Digital Input
is a registered Danfoss trademark
Function:
Present braking energy transferred
to an external brake resistor.
Stated as an instantaneous value.
Braking energy transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 seconds.
Present heatsink temperature of the
adjustable frequency drive. The cut-
out limit is 203°F ± 9°F [95° ± 5°C];
cutting back in occurs at 158°F ±9°F
[70° ± 5°C].
Percentage load of the inverters
Nominal current of the adjustable
frequency drive.
Maximum current of the adjustable
frequency drive.
State of the event executed by the
control
Temperature of the control card.
See parameter group 23-0* Timed
Actions.
percentage, i.e., the sum of analog/
pulse/bus.
Reference value from programmed
digital input(s).
View the contribution of the digital
potentiometer to the actual
reference Feedback.
View the value of Feedback 1. See
also par. 20-0*.
View the value of Feedback 2. See
also par. 20-0*.
View the value of Feedback 3. See
also par. 20-0*.
Returns the Drive Closed Loop PID
controller output value in percent.
Displays the status of the digital
inputs. Signal low = 0; Signal high =
1.
Regarding order, see 16-60 Digital
Input. Bit 0 is at the extreme right.