Parameter Description
23-61 Continuous Bin Data
Range:
0
[0 -
3
3
4294967295 ]
*
23-62 Timed Bin Data
Range:
0
[0 -
*
4294967295 ]
3-152
®
VLT
HVAC Drive Programming Guide
Function:
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the
following intervals:
Counter [0]: 0%‒<10%
Counter [1]: 10%‒<20%
Counter [2]. 20%‒<30%
Counter [3]: 30%‒<40%
Counter [4]: 40%‒<50%
Counter [5]: 50%‒<60%
Counter [6]. 60%‒<70%
Counter [7]: 70%‒<80%
Counter [8]: 80%–<90%
Counter [9]: 90%‒<100% or Max
The above minimum limits for the intervals
are the default limits. These can be changed
in 23-65 Minimum Bin Value.
Starts to count when the Adjustable
frequency drive is powered up for the first
time. All counters can be reset to 0 in
23-66 Reset Continuous Bin Data.
Function:
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating data
monitored sorted according to the intervals
as for 23-61 Continuous Bin Data.
Starts to count at the date/time
programmed in 23-63 Timed Period Start,
and stops at the time/date programmed in
23-64 Timed Period Stop. All counters can be
reset to 0 in 23-67 Reset Timed Bin Data.
MG11CD22 - VLT
23-63 Timed Period Start
Range:
Size related
[ 0 - 0 ] Set the date and time at which trending
*
and
NOTE!
The Adjustable frequency drive has no backup of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power-down unless a Real Time
Clock module with backup is installed. Consequently the
logging will be stopped until date/time is readjusted in
0-70 Date and Time. In 0-79 Clock Fault it is possible to
program for a warning in case the clock has not been set
properly, e.g., after a power-down.
NOTE!
When mounting an analog I/O MCB 109 option card, a
battery backup of the date and time is included.
23-64 Timed Period Stop
Range:
Size related
*
NOTE!
When mounting an Analog I/O MCB 109 option card, a
battery backup of the date and time is included.
23-65 Minimum Bin Value
Range:
Size related
*
23-66 Reset Continuous Bin Data
and
Option:
[0] Do not reset
[1] Do reset
®
is a registered Danfoss trademark
Function:
starts the update of the timed bin
counters.
Date format will depend on setting in
0-71 Date Format, and time format on
setting in 0-72 Time Format.
Function:
[ 0 - 0 ]
Function:
[ 0 - 100. %]
Function:
Select Do reset [1] to reset all values in
23-61 Continuous Bin Data.
After pressing OK, the setting of the parameter
value will automatically change to Do not reset
[0].