Parameter Description
3.11 Main Menu - CAN Fieldbus (Serial Communication bus) - Group 10
3.11.1 10-** DeviceNet and CAN serial
communications bus
3.11.2 10-0* Common Settings
10-00 CAN Protocol
Option:
Function:
[1]
DeviceNet
View the active CAN protocol.
*
NOTE!
The parameter options depend on installed option.
10-01 Baud Rate Select
Option:
Function:
Select the serial communication bus
transmission speed. The selection must
correspond to the transmission speed of the
master and the other serial communication
bus nodes.
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
125 Kbps
*
[21]
250 Kbps
[22]
500 Kbps
[23]
800 Kbps
[24]
1000 Kbps
10-02 MAC ID
Range:
Size related
[ 0 - 63. ]
*
10-05 Readout Transmit Error Counter
Range:
Function:
0
[0 - 255 ] View the number of CAN control transmission
*
errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
Function:
0
[0 - 255 ] View the number of CAN control receipt errors
*
since the last power-up.
10-07 Readout Bus Off Counter
Range:
Function:
0
[0 - 255 ] View the number of Bus Off events since the last
*
power-up.
®
VLT
HVAC Drive Programming Guide
3.11.3 10-1* DeviceNet
10-10 Process Data Type Selection
Option:
[0]
[1]
[2]
[3]
Function:
MG11CD22 - VLT
®
is a registered Danfoss trademark
Function:
Select the Instance (message) for data
transmission. The instances available are
dependent upon the setting of 8-10 Control
Profile.
When 8-10 Control Profile is set to [0] FC
profile, 10-10 Process Data Type Selection
options [0] and [1] are available.
When 8-10 Control Profile is set to [5] ODVA,
10-10 Process Data Type Selection options [2]
and [3] are available.
Instances 100/150 and 101/151 are Danfoss-
specific. Instances 20/70 and 21/71 are
ODVA-specific AC Drive profiles.
For guidelines in message selection, please
refer to the DeviceNet Instruction Manual.
Note that a change to this parameter will
be executed immediately.
INSTANCE
*
100/150
INSTANCE
101/151
INSTANCE
20/70
INSTANCE
21/71