Parameter Description
Par. 1-37
Par. 1-30
I
d
L
R
d
s
U
d
d-axis equivalent circuit
Par. 1-37
Par. 1-30
I
d
L
=L
R
q
d
s
U
q
q-axis equivalent circuit
Figure 3.5 Motor Equivalent Circuit Diagram for a PM Non-salient
Motor
1-30 Stator Resistance (Rs)
Range:
Function:
Size
[
0.0140 -
Set the stator resistance value.
related
140.0000 Ohm]
Enter the value from a motor data
*
sheet or perform an AMA on a
cold motor. This parameter cannot
be adjusted while the motor is
running.
1-31 Rotor Resistance (Rr)
Range:
Function:
Size
[ 0.0100 -
Fine-tuning R
related
100.0000
performance. Set the rotor resistance
*
Ohm]
value using one of these methods:
1.
2.
3.
®
VLT
HVAC Drive Programming Guide
ω
L
I
s
q
q
+
-
ω
L
I
s
d
d
+
-
+
Par. 1-40
ω
λ
s
PM
-
will improve shaft
r
Run an AMA on a cold motor.
The Adjustable frequency drive
will measure the value from the
motor. All compensations are
reset to 100%.
Enter the R
value manually.
r
Obtain the value from the
motor supplier.
Use the R
default setting. The
r
Adjustable frequency drive
establishes the setting on the
basis of the motor nameplate
data.
MG11CD22 - VLT
®
is a registered Danfoss trademark
NOTE!
1-31 Rotor Resistance (Rr) will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
1-35 Main Reactance (Xh)
Range:
Function:
Size
[
1.0000 -
Set the main reactance of the motor
related
10000.0000
using one of these methods:
*
Ohm]
1.
2.
3.
NOTE!
1-35 Main Reactance (Xh) will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
NOTE!
This parameter cannot be adjusted while running.
1-36 Iron Loss Resistance (Rfe)
Range:
Size related
[ 0 - 10000.000 Ohm]
*
NOTE!
This parameter cannot be adjusted while the motor is
running.
NOTE!
This parameter is not available from the LCP.
1-37 d-axis Inductance (Ld)
Range:
Size related
[ 0.000 - 0.000
*
mH]
Run an AMA on a cold motor.
The Adjustable frequency
drive will measure the value
from the motor.
Enter the X
value manually.
h
Obtain the value from the
motor supplier.
Use the X
default setting.
h
The Adjustable frequency
drive establishes the setting
on the basis of the motor
nameplate data.
Function:
Function:
Enter the value of the d-axis
inductance. Obtain the value from
the permanent magnet motor
data sheet.
3-19
3
3