Danfoss VLT FC 100 Series Programming Manual page 200

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

Parameter Description
NOTE!
The maximum current for the analog outputs 0–10 V is 1 mA.
NOTE!
Where Live Zero Monitoring is used, it is important that any analog inputs not being used for the frequency controller, i.e.,
being used as part of the building management system decentral I/O, should have their Live Zero function disabled.
Terminal
Parameters
Analog inputs
X42/1
26-00 Terminal X42/1
Mode, 26-1*
X42/3
26-01 Terminal X42/3
Mode, 26-2*
X42/5
26-02 Terminal X42/5
Mode, 26-3*
Analog outputs
X42/7
26-4*
X42/9
26-5*
X42/11
26-6*
Table 3.34 Relevant parameters
It is also possible to read the analog inputs, write to the analog outputs and control the relays, using communication via
the serial bus. In this instance, these are the relevant parameters.
Terminal
Parameters
Analog inputs (read)
X42/1
18-30 Analog Input
X42/1
X42/3
18-31 Analog Input
X42/3
X42/5
18-32 Analog Input
X42/5
Analog outputs (write)
X42/7
18-33 Analog Out
X42/7 [V]
X42/9
18-34 Analog Out
X42/9 [V]
X42/11
18-35 Analog Out
X42/11 [V]
Table 3.35 Relevant parameters
Setting of on-board Real Time Clock.
The Analog I/O option incorporates a real time clock with battery backup. This can be used as backup of the clock function
included in the Adjustable frequency drive as standard. See 3.2.8 0-7* Clock Settings.
The Analog I/O option can be used for the control of devices such as servos or valves, using the Extended Closed-loop
facility, thus removing control from the Building Management System. See 3.19 Main Menu - Extended Closed-loop - Group 21.
There are three independent Closed-loop PID controllers.
®
VLT
HVAC Drive Programming Guide
Terminal
Analog inputs
53
54
Analog output
42
Terminal
Parameters
Analog inputs (read)
53
16-62 Analog Input 53 Relay 1 Term 1, 2, 3
54
16-64 Analog Input 54 Relay 2 Term 4, 5, 6
Analog output (write)
42
6-53 Terminal 42
Output Bus Control
MG11CD22 - VLT
®
is a registered Danfoss trademark
Parameters
Terminal
Relays
6-1*
Relay 1 Term 1, 2, 3
6-2*
Relay 2 Term 4, 5, 6
6-5*
Terminal
Relays
NOTE!
The relay outputs must be enabled via
Control Word Bit 11 (Relay 1) and Bit 12
(Relay 2).
3
Parameters
5-4*
5-4*
Parameters
16-71 Relay Output
[bin]
16-71 Relay Output
[bin]
3-173