Parameter Description
3.9.6 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
[0 - 4194302 ] Enter a unique ID number for the BACnet
*
device.
8-72 MS/TP Max Masters
Range:
Function:
127
[1 - 127 ] Define the address of the master which holds
*
the highest address in this network.
Decreasing this value optimizes polling for the
token.
NOTE!
This parameter is active only when 8-30 Protocol is set to
[9] Adjustable Frequency Drive Option.
8-73 MS/TP Max Info Frames
Range:
Function:
1
[1 - 65534 ] Define how many info/data frames the device
*
is allowed to send while holding the token.
NOTE!
This parameter is active only when 8-30 Protocol is set to
[9] Adjustable Frequency Drive Option.
8-74 "I-Am" Service
Option:
Function:
[0]
Send at power-
*
up
[1]
Continuously
Choose whether the device should send
the "I-Am" service message only at
power-up or continuously with an
interval of approx. 1 min.
NOTE!
This parameter is active only when 8-30 Protocol is set to
[9] Adjustable Frequency Drive Option.
8-75 Initialization Password
Range:
Function:
Size related
[1 - 1 ] Enter the password needed for execution
*
of Drive Re-initialization from BACnet.
NOTE!
This parameter is active only when 8-30 Protocol is set to
[9] Adjustable Frequency Drive Option.
®
VLT
HVAC Drive Programming Guide
3.9.7 8-8* AFD Port Diagnos.
These parameters are used for monitoring the bus
communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range:
0
8-81 Bus Error Count
Range:
0
8-82 Slave Messages Rcvd
Range:
0
8-83 Slave Error Count
Range:
0
8-84 Slave Messages Sent
Range:
0
8-85 Slave Timeout Errors
Range:
0
3.9.8 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range:
100 RPM
MG11CD22 - VLT
®
is a registered Danfoss trademark
Function:
[0 - 0 ] This parameter shows the number of valid
*
messages detected on the bus.
Function:
[0 - 0 ] This parameter shows the number of messages
*
with faults (e.g., CRC fault), detected on the bus.
Function:
[0 - 0 ] This parameter shows the number of valid
*
messages addressed to the slave, sent by the
Adjustable frequency drive.
Function:
[0 - 0 ] This parameter shows the number of error
*
messages, which could not be executed by the
Adjustable frequency drive.
Function:
[0 - 0 ] This parameter shows the number of messages
*
sent from this adjustable frequency drive.
Function:
[0 - 0 ] This parameter shows the number of messages
*
suppressed due to a timeout.
Function:
[ 0 - par. 4-13
Enter the jog speed. This is a fixed
*
RPM]
jog speed activated via the serial
port or serial communication bus
option.
3
3
3-65