Danfoss VLT FC 100 Series Programming Manual page 97

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

Parameter Description
9-28 Process Control
Option:
3
3
[0]
Disable
[1]
Enable
*
cyclic
master
9-53 Profibus Warning Word
Range:
0
[0 - 65535 ] This parameter displays Profibus communi-
*
Read only
Bit:
Meaning:
0
Connection with DP master is not ok
1
Not used
2
FDLNDL (Serial Communication Bus Data link Layer) is
not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initialization of PROFIBUS is not ok
8
Adjustable frequency drive is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
Table 3.15
3-70
VLT
Function:
Process control (setting of the control word,
speed reference, and process data) is possible
via either Profibus or standard serial communi-
cation bus but not both simultaneously. Local
control is always possible via the LCP. Control
via process control is possible via either
terminals or serial communication bus
depending on the settings in 8-50 Coasting
Select to 8-56 Preset Reference Select.
Disables process control via Profibus, and
enables process control via standard serial
communication bus or Profibus Master class 2.
Enables process control via Profibus Master Class
1, and disables process control via standard
serial communication bus or Profibus Master
class 2.
Function:
cation warnings. Please refer to the Profibus
Instruction Manual for further information.
MG11CD22 - VLT
®
HVAC Drive Programming Guide
9-63 Actual Baud Rate
Option:
[0]
9.6 kbit/s
[1]
19.2 kbit/s
[2]
93.75 kbit/s
[3]
187.5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31.25 kbit/s
[11]
45.45 kbit/s
[255]
No baud rate found
*
9-65 Profile Number
Range:
0
[0 - 0 ] This parameter contains the profile identification.
*
NOTE!
This parameter is not visible via LCP.
9-70 Programming Set-up
Option:
[0]
Factory setup Uses default data. This option can be used
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up Follows the active set-up selected in
*
This parameter is unique to LCP and serial communication
busses. See also 0-11 Programming Set-up.
®
is a registered Danfoss trademark
Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
Function:
Byte 1 contains the profile number and byte 2 the
version number of the profile.
Function:
Select the set-up to be edited.
as a data source to return the other set-ups
to a known state.
Edits Set-up 1.
Edits Set-up 2.
Edits Set-up 3.
Edits Set-up 4.
0-10 Active Set-up.