Limitation Of The Load Range - Siemens LMV5 Series Basic Documentation

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Limitation of the
load range
64/278
Siemens Building Technologies
HVAC Products
The curves are defined by the 2 limits «Low-fire» (part load) and «Nominal load»
(maximum load).
In certain cases, it has proven practical to limit the burner's output, either temporarily or
permanently.
This limitation of the burner's working range can make sense in both directions. The
burner's working range then looks as follows:
Pos.
7550d06E
Limited working range
The usable output range always lies within the defined curves. This means that if the
minimum load is smaller than the low-fire load, loads below the low-fire load will be
disregarded. And if the maximum load is greater than the high-fire load, loads above
the high-fire load will be disregarded.
If the minimum load is greater than or equal to the low-fire load, the minimum load
assumes the role of the low-fire load, that is, after ignition, the minimum load will be
considered.
The 2 parameters «Minimum load» and «Maximum load» can be set depending on the
type of fuel burnt, whereby:
Low-fire load ≤ minimum load ≤ maximum load ≤ nominal load
Parameter:
MinLoadGas
Parameter:
MaxLoadGas
Parameter:
MinLoadOil
Parameter:
MaxLoadOil
Basic Documentation LMV51...
5 Fuel / air ratio control (FARC)
AIR
FUEL
AUX
Load
CC1P7550en
01.10.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents