The only difference between this example and the first example is the event identifier of 3 to show a restore for the
system tamper alarm and the checksum value.
SIA 1, SIA 2, SIA 3, Extended SIA 3 and Extended SIA 3 V2
The SIA formats transmit data from the log book entries to the ARC (ESCC).
The four SIA formats differ based on the data volume that is transferred with each message.
Type
SIA1
SIA2
SIA3
Extended SIA 3
Extended SIA 3 V2
Extended SIA 3 V3
Whereby:
AAAAAA
"N"
"ti"hh:mm/
"id"nnn/
"ri"nn/
CC
cc
"A"S
Note:
The alarm control panel sends
table above.
Example
The different formats for the SIA protocol appear as follows in the event of a fire alarm in zone 2 of partition 4 at 10:15
with the account number 10 for partition 4:
SIA1
SIA2
SIA3
Extended SIA3
Extended SIA3 V2
Extended SIA3 V3
Note about Extended SIA3 V2:
Format
#AAAAAA|NCCcc
#AAAAAA|Nidnnn/rinn/CCcc
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc
#AAAAAA|AS
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS
#AAAAAA|Ntihh:mm|idnnn|rinn|CCcc|AS
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc^AS^
Adjustable 6-digit account number (e.g. 123456).
New event (always N)
Time (e.g. ti10:23/).
User number, when usable, otherwise not sent (e.g. id123/ or id6/)
Partition number (e.g. ri12/ or ri3).
Event code (e.g. FA = Fire Alarm).
Zone or control panel number, when usable, otherwise not sent (e.g. 23 or 5)
Text description of the event, usually a description of the log book event
the characters that are between " and " shown above exactly as they are listed in the
#000010|NFA2
#000010|N/ri4/FA2
#000010|Nti10:15/ri4/FA2
#000010|AFire Zone 2
#000010|Nti10:15/ri4/FA2/AFire Zone 2
#000010|Nti10:15|ri4|FA2|AFire Zone 2
#000010|Nti10:15/ri4/FA2^AFire Zone 2^