Configuration
Ethernet – IP Mobile
IP Mobile
190
Push notifications
The push notification only functions via the wireless mobile module (IP mobile) if a
PPP connection (point to point protocol, IP mobile) is already active/configured for
another service (e.g. e-mail).
E-mail must be at least enabled. However, no e-mails need to be sent. Configure
the settings for this accordingly.
Configure ABUS server, app and push via Ethernet.
There must be an IP mobile fault (e.g. no longer logged into a wireless mobile net-
work) for the IP stack to switch to Ethernet.
Ethernet is used first. 4G/2G is only used when there is an Ethernet fault.
This setting is recommended in order to establish a redundant, IP-based transmis-
sion path for ARC/ESCC reporting, e-mail and push.
Note
Ethernet faults must first be detected by the alarm panel.
Danger
Ethernet is still used for
access to the web server via a web browser
APP access
for push notifications (SW <= v3.01.01)
For cameras in the local network
It is not possible to access the alarm panel with the app via the ABUS server and
via IP mobile. It is not possible to access the web server of the alarm panel via IP
mobile.
Note
Push notifications
The push notification only functions via the wireless mobile module (IP mobile) if a
PPP connection (point to point protocol, IP mobile) is already active/configured for
another service (e.g. e-mail).
E-mail must be at least enabled. However, no e-mails need to be sent. Configure
the settings for this accordingly.
Configure ABUS server, app and push via Ethernet.
There must be an Ethernet fault for the IP stack to switch to IP mobile.
Only 4G/2G is used, Ethernet is not used.
Note
Danger
Ethernet is still used for
access to the web server via a web browser
APP access
for push notifications (SW <= v3.01.01)