Appendix
3. PARTITIONS
Partition 1-4
Name
Complete arming
Output Mode
Exit Time
Settle Time
Entry Time
Alarm Response
Siren delay
Ext. Siren Time
Strobe on Set
Strobe on Unset
Beep on Set
Beep on Unset
Int. Siren Time
Part set
Output Mode
Exit Time
Settle Time
Entry Time
Alarm Response
Siren delay
Ext. Siren Time
Pt.Set Final Exit
Pt.Set Entry Route
Strobe on Set
Strobe on Unset
Beep on Set
Beep on Unset
Int. Siren Time
310
Partition n
Timed Set
40 seconds
15 seconds
40 seconds
Siren + Comms
0 minutes
15 minutes
3 minutes when country = Germany
Off
Off
Off
Off
Endless
Instant Set
40 seconds
15 seconds
40 seconds
Siren
0 minutes
15 minutes
3 minutes when country = Germany
Final Door
Entry Route
Off
Off
Off
Off
Endless
Partition 1 to 4
Only appears if the "Timed Set" or
"Silent Set" Output Mode is set.
Only appears if the "Final Door Set",
"Lock Set" or "Cancel Exit Delay"
Output Mode is set.
To fulfil EN50131-1 Clause 8.3.8.2,
maximum of 45 s
Internal alarm included
To fulfil EN 50131-1 Clause 8.6,
minimum 90 s, maximum 15 min.
This setting is required to fulfil
EN 50131.
This setting is required to fulfil
EN 50131.
Only appears if the "Timed Set" or
"Silent Set" Output Mode is set.
Only appears if the "Final Door Set",
"Lock Set" or "Cancel Exit Delay"
Output Mode is set
To fulfil EN50131-1 Clause 8.3.8.2,
maximum of 45 s
Internal alarm included
This setting is required to fulfil
EN 50131.
To fulfil EN 50131-1 Clause 8.6,
minimum 90 s, maximum 15 min.
This setting is required to fulfil
EN 50131.
This setting is required to fulfil
EN 50131.