Data Types Supported By The Frequency Converter; Conversion; Examples - Danfoss VLT DriveMotor FCP 106 Programming Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

RS485 Installation and Set-...
capable of reading parameters containing data type 9 (text
string).
Parameter 15-40 FC Type to parameter 15-53 Power Card
Serial Number contain data type 9.
3
3
For example, read the unit size and mains voltage range in
parameter 15-40 FC Type. When a text string is transferred
(read), the length of the telegram is variable, and the texts
are of different lengths. The telegram length is defined in
the 2nd byte of the telegram (LGE). When using text
transfer, the index character indicates whether it is a read
or a write command.
To read a text via the PWE block, set the parameter
command (AK) to F hex. The index character high-byte
must be 4.
3.4.11 Data Types Supported by the
Frequency Converter
Unsigned means that there is no operational sign in the
telegram.
Data types
3
4
5
6
7
9
Table 3.8 Data Types

3.4.12 Conversion

The various attributes of each parameter are shown in
chapter 4 Parameters. Parameter values are transferred as
whole numbers only. Conversion factors are used to
transfer decimals.
Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion
factor of 0.1. To preset the minimum frequency to 10 Hz,
transfer the value 100. A conversion factor of 0.1 means
that the value transferred is multiplied by 0.1. The value
100 is thus perceived as 10.0.
22
®
VLT
DriveMotor FCP 106/FCM 106
Description
Integer 16
Integer 32
Unsigned 8
Unsigned 16
Unsigned 32
Text string
Danfoss A/S © 11/2015 All rights reserved.
Conversion index
74
2
1
0
-1
-2
-3
-4
-5
Table 3.9 Conversion
3.4.13 Process Words (PCD)
The block of process words is divided into 2 blocks of 16
bits, which always occur in the defined sequence.
PCD 1
Control telegram (master⇒slave control word) Reference value
Control telegram (slave⇒master) status word
Table 3.10 Process Words (PCD)

3.5 Examples

3.5.1 Writing a Parameter Value
Change parameter 4-14 Motor Speed High Limit [Hz] to 100
Hz.
Write the data in EEPROM.
PKE=E19E hex - Write single word in parameter 4-14 Motor
Speed High Limit [Hz]:
IND=0000 hex.
PWEHIGH=0000 hex.
PWELOW=03E8 hex.
Data value 1000, corresponding to 100 Hz, see
chapter 3.4.12 Conversion.
The telegram looks like Illustration 3.11.
E19E
H
0000
H 0000
PKE
IND
PWE
Illustration 3.11 Telegram
Conversion factor
3600
100
10
1
0.1
0.01
0.001
0.0001
0.00001
PCD 2
Present output
frequency
H 03E8
H
PWE
high
low
MG03N202

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt drivemotor fcm 106

Table of Contents