Parameters
16-12 Motor Voltage
Range:
Function:
0 V
[0 - 65535 V] View the motor voltage, a calculated value
*
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
[0 - 6553.5 Hz] View the motor frequency, without
*
resonance damping.
16-14 Motor current
Range:
Function:
0 A
[0 - 655.35 A] View the motor current measured as an
*
average value, I
16-15 Frequency [%]
Range:
Function:
0 %
[0 -
View a 2-byte word reporting the actual
*
6553.5 %]
motor frequency (without resonance
damping) as a percentage (scale 0000–4000
hex) of parameter 4-19 Max Output
Frequency.
16-16 Torque [Nm]
Range:
Function:
0
[-3000
View the torque value with sign, applied to the
Nm
- 3000
motor shaft. Linearity is not exact between
*
Nm]
160% motor current and torque in relation to
the rated torque. Some motors supply more
than 160% torque. Therefore, the minimum
value and the maximum value depend on the
maximum motor current and the motor used.
The value is filtered, and thus approximately 30
ms may pass from when an input changes
value to when the data readout values change.
In flux control principle, this readout is
compensated for inparameter 1-68 Motor Inertia
for improved accuracy.
16-18 Motor Thermal
Range:
Function:
0 %
[0 -
View the calculated motor temperature in
*
100 %]
percentage of allowed maximum. At 100%, a trip
occurs, if selected in parameter 1-90 Motor
Thermal Protection. The basis for the calculation
is the ETR function selected in
parameter 1-90 Motor Thermal Protection.
MG03N202
Programming Guide
.
RMS
Danfoss A/S © 11/2015 All rights reserved.
4.13.3 16-2*
16-22 Torque [%]
Range:
Function:
0 %
[ -200 - 200 % ] View the torque in percent of nominal
*
torque, with sign, applied to the motor
shaft.
16-26 Power Filtered [kW]
Range:
Function:
0 kW
[0 - 1000
Motor power consumption. The value shown
*
kW]
is calculated on basis of the real-time motor
voltage and motor current. The value is
filtered, and a few seconds may pass between
the input value change and the data readout
value change.
16-27 Power Filtered [hp]
Range:
Function:
0 hp
[0 - 1000
Motor power in hp. The value shown is
*
hp]
calculated based on real-time motor voltage
and motor current. The value is filtered, and a
few seconds may pass between the input
value change and the data readout value
change.
4.13.4 16-3* Drive Status
16-30 DC Link Voltage
Range:
Function:
0 V
[0 - 65535 V]
Shows the actual DC-link voltage.
*
16-34 Heatsink Temp.
Range:
Function:
0 °C
[-128 - 127 °C] View the heat sink temperature of the
*
frequency converter.
16-35 Inverter Thermal
Range:
Function:
0 %
[0 - 255 %] View the percentage of thermal load on the
*
frequency converter. At 100%, a trip occurs.
16-36 Inv. Nom. Current
Range:
Function:
0 A
[0 - 655.35 A] View the inverter nominal current. The data
*
is used for motor overload protection, and
so on.
16-37 Inv. Max. Current
Range:
Function:
0 A
[0 - 655.35 A] View the inverter maximum current. The
*
data is used for calculation of frequency
converter protection, and so on.
4
4
97