Danfoss VLT DriveMotor FCP 106 Programming Manual page 58

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
4-51 Warning Current High
Range:
Size
[ 0.0 -
related
194.0 A]
*
4
4
4-54 Warning Reference Low
Range:
-4999
[-4999 -
*
4999 ]
4-55 Warning Reference High
Range:
4999
[-4999 -
*
4999 ]
4-56 Warning Feedback Low
Range:
-4999
ProcessCtrlUnit
4-57 Warning Feedback High
Range:
4999
ProcessCtrlUnit
56
Function:
Enter the I
value. When the motor
HIGH
current exceeds this limit, a bit in the
status word is set. This value can also be
programmed to produce a signal on the
digital output or the relay output.
Function:
Enter the lower reference limit. When the
actual reference drops below this limit, the
display reads Ref
. The signal outputs can
LOW
be programmed to produce a status signal
on terminal 27 or 29 and on relay output 01
or 02.
Function:
Use this parameter to set a higher limit for the
reference range.
When the actual reference exceeds this limit,
the display reads Reference High. Warning bit
19 is set in parameter 16-94 Ext. Status Word.
The output relay or the digital output can be
configured to indicate this warning. The LCP
warning indicator light is not turned on when
this parameter set limit is reached.
Function:
[-4999 - 4999
Use this parameter to set a
ProcessCtrlUnit]
lower limit for the feedback
*
range.
When the feedback drops
below this limit, the display
reads Feedback Low. Warning
bit 6 is set in
parameter 16-94 Ext. Status
Word. The output relay or
digital output can be
configured to indicate this
warning. The LCP warning
indicator light does not light
up when this parameter set
limit is reached.
Function:
[-4999 - 4999
Use this parameter to set a
ProcessCtrlUnit]
higher limit for the feedback
*
range.
When the feedback exceeds
this limit, the display reads
Feedback High. Warning bit 5
Danfoss A/S © 11/2015 All rights reserved.
®
VLT
DriveMotor FCP 106/FCM 106
4-57 Warning Feedback High
Range:
4-58 Missing Motor Phase Function
Option:
[0]
Off No alarm is shown if a missing motor phase occurs.
[1]
On An alarm is shown if a missing motor phase occurs.
*
4.5.4 4-6* Speed Bypass
Define the speed bypass areas for the ramps. 3 frequency
ranges can be avoided.
4-61 Bypass Speed From [Hz]
Range:
0 Hz
*
Hz]
4-63 Bypass Speed To [Hz]
Range:
0 Hz
*
Hz]
4.5.5 Semi-Automatic Bypass Speed Set-up
Use the semi-automatic bypass speed set-up to facilitate
the programming of the frequencies to be skipped due to
resonances in the system.
Procedure:
1.
NOTICE
Adjust the ramp times in parameter 3-41 Ramp 1 Ramp
Up Time and parameter 3-42 Ramp 1 Ramp Down Time.
2.
3.
Function:
is set in parameter 16-94 Ext.
Status Word. The output relay
or digital output can be
configured to indicate this
warning. The LCP warning
indicator light does not light
up when this parameter set
limit is reached.
Function:
Function:
[ 0 - 500
Some systems call for avoiding certain
output speeds due to resonance problems
in the system. Enter the lower limits of the
speeds to be avoided.
Function:
[ 0 - 500
Some systems call for avoiding certain
output speeds due to resonance problems
in the system. Enter the upper limits of the
speeds to be avoided.
Stop the motor.
Select [1] Enabled in parameter 4-64 Semi-Auto
Bypass Set-up.
Press [Hand On] to start the search for frequency
bands causing resonances. The motor ramps up
according to the ramp set.
MG03N202