Parameters
16-71 Relay Output [bin]
Range:
Function:
0
[0 - 65535 ] View the setting of the relay.
*
Bits definition:
Bit 0~2
Bit 3
Bit 4
Bit 5~15
Table 4.12 Relay Setting
16-72 Counter A
Range:
Function:
0
[-32768 -
View the present value of counter A. Counters are
*
32767 ]
useful as comparator operands, see
parameter 13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital
Inputs) or by using an SLC action
(parameter 13-52 SL Controller Action).
16-73 Counter B
Range:
Function:
0
[-32768 -
View the present value of counter B. Counters are
*
32767 ]
useful as comparator operands
(parameter 13-10 Comparator Operand).
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital
Inputs) or by using an SLC action
(parameter 13-52 SL Controller Action).
16-79 Analog Output AO45
Range:
Function:
0 mA
[0 - 20
View the actual value at output 45 in mA.
*
mA]
The value shown reflects the selection in
parameter 6-70 Terminal 45 Mode and
parameter 6-71 Terminal 45 Analog Output.
4.13.7 16-8* Fieldbus & FC Port
Parameters for reporting the bus references and control
words.
16-80 Fieldbus CTW 1
Range:
Function:
0
[0 -
View the 2-byte control word (CTW) received
*
65535 ]
from the bus master. Interpretation of the CTW
depends on the fieldbus option installed and the
CTW profile selected in parameter 8-10 Control
Word Profile. For more information, see relevant
fieldbus manuals.
MG03N202
Programming Guide
Unused
Relay 02
Relay 01
Unused
Danfoss A/S © 11/2015 All rights reserved.
16-82 Fieldbus REF 1
Range:
Function:
0
[-32768 -
To set the reference value, view the 2-byte
*
32767 ]
word sent with the control word from the
bus master. For more information, refer to
the relevant fieldbus manual.
16-84 Comm. Option STW
Range:
Function:
0
[0 - 65535 ] View the extended fieldbus communication
*
option status word. For more information, refer
to the relevant fieldbus manual.
16-85 FC Port CTW 1
Range:
Function:
1084
[0 -
View the 2-byte control word (CTW) received
*
65535 ]
from the bus master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile
selected in parameter 8-10 Control Word
Profile.
16-86 FC Port REF 1
Range:
Function:
0
[-32768 - 32767 ] View the last received reference from the
*
FC port.
4.13.8 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range:
Function:
0
[0 - 0xFFFFFFFFUL ] View the alarm word sent via the serial
*
communication port in hex code.
16-91 Alarm Word 2
Range:
Function:
0
[0 - 0xFFFFFFFFUL ] View the alarm word 2 sent via the
*
serial communication port in hex code.
16-92 Warning Word
Range:
Function:
0
[0 - 0xFFFFFFFFUL ] View the warning word sent via the
*
serial communication port in hex code.
16-93 Warning Word 2
Range:
Function:
0
[0 - 0xFFFFFFFFUL ] View the warning word 2 sent via the
*
serial communication port in hex code.
4
4
99