Parameters
6-92 Terminal 42 Digital Output
Option:
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
4
4
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[191] Dry Pump
[192] End Of Curve
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
0 %
[0 -
*
200 %]
6-94 Terminal 42 Output Max Scale
Range:
100
[0 -
%
200 %]
*
6-96 Terminal 42 Output Bus Control
Range:
0
[0 - 16384 ] Holds the analog output at terminal 42 if
*
70
VLT
Function:
Function:
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 42. Set the
value to be the percentage of the full range
of the variable selected in parameter 6–
91 Terminal 42 Analog Output.
Function:
Scale for the maximum output (20 mA) of the
scaling at terminal 42. Set the value to be the
percentage of the full range of the variable
selected in parameter 6–91 Terminal 42 Analog
Output.
Current
(mA)
20
0/4
0%
Analog
Analog
100%
output
Output
Min Scale
Max Scale
par. 6-93
par. 6-94
Illustration 4.15 Output Maximum Scale
Function:
controlled by bus.
Danfoss A/S © 11/2015 All rights reserved.
®
DriveMotor FCP 106/FCM 106
Variable
for
output
example:
Power
MG03N202