Main Menu - Application Functions - Group; Main Menu - Application Functions 2 - Group - Danfoss VLT DriveMotor FCP 106 Programming Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
4.16 Main Menu - Application Functions -
Group 22
22-01 Power Filter Time
Range:
0.50 s
[0.02 - 10 s] Set the time constant for the filtered
*
4
4
4.16.1 22-2* No-Flow Detection
No ow/low
speed detection
Low Power
detected
Low speed
detected
Illustration 4.19 No-flow Detection
The frequency converter includes functions for detecting if the load conditions in the system allow the motor to be
stopped:
Low power detection.
Low speed detection.
One of these 2 signals must be active for a set time (parameter 22-24 No-Flow Delay) before selected action takes place.
Possible actions to select (parameter 22-23 No-Flow Function):
No action
Warning
Alarm
Sleep mode
104
VLT
Function:
power readout. A higher value gives a
more steady readout, but a slower system
response to changes.
P 22-21
1
Detection
timer
P 22-22
P 22-24
Danfoss A/S © 11/2015 All rights reserved.
®
DriveMotor FCP 106/FCM 106
22-02 Sleepmode CL Control Mode
Option:
[0]
Normal
*
[1]
Simplified The feedback is not detected. Only sleep speed
This parameter is for sleep mode running in process close
loop mode. Use this parameter to configure whether to
detect the feedback for sleep mode.
External
sleep mode
command
O
Warning
Alarm
P 22-23
Function:
The feedback is detected. Some parameters are
checked.
and time are checked.
Sleep mode
Sleep
Min run
mode
timer
1
Min sleep
timer
P 22-40
P 22-41
Cascade
controller
(destaging
command)
P 25-26
MG03N202

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT DriveMotor FCP 106 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vlt drivemotor fcm 106

Table of Contents