Danfoss VLT DriveMotor FCP 106 Programming Manual page 61

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
Digital input
Description
function
[11] Start reversing
Use for start/stop and for reversing at the
same time. Signals on [8] start are not
allowed at the same time. 0=stop, 1=start
reversing.
[14] Jog
Used for activating jog speed. See
parameter 3-11 Jog Speed [Hz]. (Default
digital input 29).
[16] Preset ref bit 0
Enables a selection of 1 of the 8 preset
references according to Table 4.5.
[17] Preset ref bit 1
Enables a selection of 1 of the 8 preset
references according to Table 4.5.
[18] Preset ref bit 2
Enables a selection of 1 of the 8 preset
references according to Table 4.5.
[19] Freeze reference Freeze actual reference. The frozen
reference is now the point of enable/
condition for speed up and speed down
to be used. If speed up/speed down is
used, a speed change always follows ramp
2 (parameter 3-51 Ramp 2 Ramp Up Time
and parameter 3-52 Ramp 2 Ramp Down
Time) in the range
parameter 3-02 Minimum Reference -
parameter 3-03 Maximum Reference.
[20] Freeze output
Freezes actual reference. The frozen
reference is now the point of enable/
condition for speed up and speed down
to be used. If speed up/speed down is
used, the speed change always follows
ramp 2.
[21] Speed up
For digital control of the up/down speed
(motor potentiometer). Activate this
function by selecting either freeze
reference or freeze output. When speed
up is activated for less than 400 ms, the
resulting reference is increased by 0.1%. If
speed up is activated for more than 400
ms, the resulting reference ramps
according to ramp 1 in
parameter 3-41 Ramp 1 Ramp Up Time.
[22] Speed down
Same as [21] Speed up, but reference
decreases.
[23] Set-up select bit
Selects 1 of the 2 set-ups. Set
0
parameter 0-10 Active Set-up to multi set-
up.
[32] Pulse Input
Select pulse input when using a pulse
sequence as either reference or feedback.
Scaling is done in parameter group 5-5*
Pulse Input. Available only for terminal 29.
[34] Ramp bit 0
Select which ramp to use. Logic 0 selects
ramp 1, while logic 1 selects ramp 2.
[37] Fire mode
A signal applied puts the frequency
converter into fire mode and disregards all
other commands. See 24-0* Fire Mode.
MG03N202
Programming Guide
Digital input
function
[52] Run permissive
[53] Hand Start
[54] Auto start
[60] Counter A (up)
[61] Counter A
(down)
[62] Reset Counter A Input for reset of counter A.
[63] Counter B (up)
Danfoss A/S © 11/2015 All rights reserved.
Description
The input terminal, for which the run
permissive is programmed, must be logic
1 before a start command can be
accepted. Run permissive has a logic AND
function related to the terminal, which is
programmed for [8] Start, [14] Jog, or [20]
Freeze Output. To start running the motor,
both conditions must be fulfilled. If run
permissive is programmed on multiple
terminals, run permissive only has to be
logic 1 on 1 of the terminals for the
function to be carried out. Run permissive
does not affect the digital output signal
for run request ([8] Start, [14] Jog, or [20]
Freeze Output) programmed in parameter
group 5-3* Digital Outputs, or parameter
group 5-4* Relays,.
NOTICE
If no run permissive signal is applied
but either run, jog, or freeze
commands is activated, the status
line in the display shows either Run
Requested, Jog Requested, or Freeze
Requested.
A signal applied puts the frequency
converter into hand on mode as if [Hand
On] is pressed and a normal stop
command is overridden. If the signal is
disconnected, the motor stops. To make
any other start commands valid, assign
another digital input to Auto Start and
apply a signal. The [Hand On] and [Auto
On] keys have no impact. The [Off] key
overrides Hand Start and Auto Start. Press
either [Hand On] or [Auto On] to
reactivate Hand Start and Auto Start. If
there is no signal on Hand Start or Auto
Start, the motor stops regardless of any
normal start command applied. If a signal
is applied to both Hand Start and Auto
Start, the function is Auto Start.
A signal applied puts the frequency
converter into Auto mode as if [Auto On]
is pressed. See also [53] Hand Start.
Input for increment counting in the SLC
counter.
Input for decrement counting in the SLC
counter.
Input for increment counting in the SLC
counter.
4
4
59