Parameters
13-01 Start Event
Option:
Function:
[26]
Logic rule 0
Use the result of logic rule 0 in the logic
rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the logic
rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the logic
rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the logic
rule.
[33]
Digital input
Use the value of DI18 in the logic rule
DI18
(High=true).
[34]
Digital input
Use the value of DI19 in the logic rule
DI19
(High=true).
[35]
Digital input
Use the value of DI27 in the logic rule
DI27
(High=true).
[36]
Digital input
Use the value of DI29 in the logic rule
DI29
(High=true).
[39]
Start
This event is true if the frequency
command
converter is started (either via digital
*
input, fieldbus or other).
[40]
Drive stopped
This event is true if the frequency
converter is stopped or coasted (either via
digital input, fieldbus, or other).
[42]
Auto Reset
This event is true if the frequency
Trip
converter is tripped (but not trip-locked)
and an automatic reset is issued.
[50]
Comparator 4
Use the result of comparator 4 in the logic
rule.
[51]
Comparator 5
Use the result of comparator 5 in the logic
rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic
rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic
rule.
[83]
Broken Belt
A broken-belt condition is detected.
Enable this function in
parameter 22-60 Broken Belt Function.
13-02 Stop Event
Option:
Function:
Select the condition (true or false)
which deactivates the smart logic
controller.
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
MG03N202
Programming Guide
13-02 Stop Event
Option:
[8]
Below I low
[9]
Above I high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[39]
Start command
[40]
Drive stopped
*
[42]
Auto Reset Trip
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-03 Reset SLC
Option:
[0]
Do not reset
*
SLC
[1]
Reset SLC
Danfoss A/S © 11/2015 All rights reserved.
Function:
Function:
Retains programmed settings in all group
13 parameters (13-** Smart Logic).
Resets all group 13 parameters (13-** Smart
Logic) to default settings.
4
4
83