Danfoss VLT DriveMotor FCP 106 Programming Manual page 120

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Diagnostics and Troubleshoo...
Alarm/
warning
Fault text
number
2
Live zero error
3
No motor
5
5
4
Mains ph. loss
7
DC over volt
8
DC under volt
Inverter
9
overload
10
Motor ETR over
11
Motor th over
13
Over Current
14
Earth Fault
16
Short Circuit
Control word
17
timeout
24
Fan fault
30
U phase loss
31
V phase loss
32
W phase loss
34
Fieldbus fault
35
Option fault
36
Mains failure
38
Internal fault
40
Overload T27
41
Overload T29
Gate drive
46
voltage fault
Control voltage
47
fault
51
AMA U
52
AMA low I
AMA motor too
53
big
AMA motor too
54
small
AMA parameter
55
out of range
118
VLT
Warning
Alarm
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
, I
X
nom
nom
X
nom
X
X
X
Danfoss A/S © 11/2015 All rights reserved.
®
DriveMotor FCP 106/FCM 106
Trip lock Cause of problem
Signal on terminal 53 or 54 is less than 50% of value set in:
Parameter 6-10 Terminal 53 Low Voltage.
Parameter 6-12 Terminal 53 Low Current.
Parameter 6-20 Terminal 54 Low Voltage.
Parameter 6-22 Terminal 54 Low Current.
See also parameter group 6–0* Analog In/Out.
A motor has not been connected to the frequency converter.
Missing phase on supply side or excess voltage imbalance. Check
X
supply voltage. See parameter 14-12 Function at Mains Imbalance.
DC-link voltage exceeds limit.
DC-link voltage is lower than voltage warning low-limit.
More than 100% load for too long.
Motor is overheated due to more than 100% load for too long. See
parameter 1-90 Motor Thermal Protection.
Thermistor or thermistor connection is disconnected. See
parameter 1-90 Motor Thermal Protection.
X
Inverter peak current limit is exceeded.
X
Discharge from output phases to ground.
X
Short circuit in motor or on motor terminals.
No communication to frequency converter. See parameter group 8-0*
Comm. and Options.
External fans have failed either due to defect hardware, or due to
missing fans.
Motor phase U is missing. Check the phase. See parameter 4-58 Missing
X
Motor Phase Function.
Motor phase V is missing. Check the phase. See parameter 4-58 Missing
X
Motor Phase Function.
Motor phase W is missing. Check the phase. See parameter 4-58 Missing
X
Motor Phase Function.
X
Contact the local Danfoss supplier.
X
X
24 V DC is possibly overloaded.
The setting of motor voltage, motor current, and motor power is
presumably wrong. Check the settings.
The motor current is too low. Check the settings.
The motor is too large to perform AMA.
The motor is too small to perform AMA.
The parameter values found from the motor are outside acceptable
range.
MG03N202