Specifications
7.2 Electrical Data
7.2.1 Mains Supply 3x380–480 V AC Normal and High Overload
Enclosure
1)
Overload
Typical shaft
output [kW]
Typical shaft
output [hp]
Maximum cable
cross-section in
2)
terminals
(mains, motor)
[mm
2
/AWG]
Output current
7
7
40 °C ambient temperature
Continuous
(3x380–440 V) [A]
Intermittent
(3x380–440 V) [A]
Continuous
(3x440–480 V) [A]
Intermittent
(3x440–480 V) [A]
Maximum input current
Continuous
(3x380–440 V) [A]
Intermittent
(3x380–440 V) [A]
Continuous
(3x440–480 V) [A]
Intermittent
(3x440–480 V) [A]
Maximum mains
fuses
Estimated power
loss [W], best
case/typical
3)
Efficiency [%], best
4)5)
case/typical
Table 7.10 Mains Supply 3x380–480 V AC Normal and High Overload: MH1, MH2, and MH3 Enclosure
1) NO: Normal overload, 110% for 1 minute. HO: High overload, 160% for 1 minute.
A frequency converter intended for HO requires a corresponding motor rating. For example, Table 7.10 shows that a 1.5 kW motor for HO requires
a P2K2 frequency converter.
2) Maximum cable cross-section is the largest cable cross-section that can be attached to the terminals. Always observe national and local
regulations.
3) Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50-598-2, refer to
www.danfoss.com/vltenergyefficiency.
4) Efficiency measured at nominal current. For energy efficiency class, see chapter 7.5 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
5) Measured using 4 m screened motor cables at rated load and rated frequency.
46
VLT® DriveMotor FCP 106/FCM 106
MH1
PK55
PK75
P1K1
NO
HO
NO
HO
0.55
0.75
0.75
1.0
4/12
4/12
1.7
2.2
1.9
2.7
2.4
3.5
1.6
2.1
1.8
2.6
2.3
3.4
1.3
2.1
1.4
2.0
2.3
2.6
1.2
1.8
1.3
1.9
2.0
2.5
See chapter 7.10 Fuse and Circuit Breaker Specifications.
38
44
0.96
0.97
Danfoss A/S © 11/2015 All rights reserved.
P1K5
P2K2
NO
HO
NO
HO
1.1
1.5
1.5
2.0
4/12
4/12
3.0
3.7
3.3
4.8
4.1
5.9
2.8
3.4
3.1
4.5
3.7
5.4
2.4
3.5
2.6
3.7
3.9
4.6
2.2
2.9
2.4
3.5
3.2
4.2
57
73
0.97
0.97
MH2
P3K0
P4K0
NO
HO
NO
HO
2.2
3.0
3.0
4.0
4/12
4/12
5.3
7.2
5.8
8.5
7.9
11.5
4.8
6.3
5.3
7.7
6.9
10.1
4.7
6.3
5.2
7.0
6.9
9.6
3.9
5.3
4.3
6.3
5.8
8.4
91
129
0.97
0.97
MH3
P5K5
NO
HO
4.0
5.0
4/12
9.0
9.9
14.4
8.2
9.0
13.2
8.3
9.1
12.0
6.8
7.5
11.0
143
0.97
MG03L302