Parameters
4.8.3 8-3* FC Port Settings
8-30 Protocol
Option:
4
4
[0]
FC
*
[2]
Modbus
RTU
[4]
FLN
[5]
BACNet
8-31 Address
Range:
1
[ 0.0 - 247 ] Enter the address for the RS485 port. Valid
*
8-32 Baud Rate
Option:
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity / Stop Bits
Option:
[0] Even Parity, 1 Stop
Bit
[1] Odd Parity, 1 Stop
Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop
Bits
72
VLT
Function:
Select the protocol for the integrated RS485
port. Change of settings in
parameter 8-30 Protocol may change the baud
rate.
Communication according to the FC Protocol.
Communication according to the Modbus RTU
protocol.
Function:
range: 1–126 for FC-bus, or 1–247 for Modbus.
Function:
Select the baud rate for the RS485 port
Default refers to the FC protocol. Changing the
protocol in parameter 8-30 Protocol may
change the baud rate.
Changing protocol in parameter 8-30 Protocol
may change the baud rate.
Default setting for FLN.
Default setting for BACnet.
Default setting for Modbus RTU.
Function:
Parity and stop bits for the protocol
using the FC port. For some of the
protocols, not all options are available.
Default refers to the FC protocol.
Changing protocol in parameter 8–30
Protocol may change the baud rate.
Danfoss A/S © 11/2015 All rights reserved.
®
DriveMotor FCP 106/FCM 106
8-35 Minimum Response Delay
Range:
0.01 s
[ 0.0010 - 0.5
*
s]
8-36 Maximum Response Delay
Range:
Size
related
*
8-37 Maximum Inter-char delay
Range:
0.025 s
[0.025 - 0.025
*
s]
4.8.4 8-4* MC Protocol Set
8-40 Telegram Selection
Option:
[1]
Standard telegram 1
*
[300] Standard telegram
FCM300
8-42 PCD Write Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs.
The number of PCDs depends on the PPO type.
The values in PCD 3–10 are written to the selected parameters as
data values.
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
Function:
Specify the minimum delay time
between receiving a request and
transmitting a response. This minimum
delay time is used for overcoming
modem turnaround delays.
Function:
[ 0.1 -
Specify the maximum permissible
10.0 s]
delay time between receiving a
request and transmitting the response.
If this time is exceeded, no response is
returned.
Function:
Specify the maximum permissible time
interval between receipt of 2 bytes.
This parameter activates timeout if
transmission is interrupted.
Function:
Enables use of freely configurable
telegrams or standard telegrams for
the FC Port.
None
[302] Minimum Reference
[303] Maximum Reference
[341] Ramp 1 Ramp up time
[342] Ramp 1 Ramp down time
[351] Ramp 2 Ramp up time
[352] Ramp 2 Ramp down time
[380] Jog Ramp Time
[381] Quick Stop Time
[412] Motor Speed Low Limit
[Hz]
[414] Motor Speed High Limit
[Hz]
Function:
MG03N202