Diagnostics and Troubleshoo...
Alarm/
warning
Fault text
number
AMA
56
interrupted by
user
57
AMA time-out
58
AMA internal
59
Current limit
External
60
Interlock
63
Mech. brake
low
65
Ctr. card temp
Heat sink
66
temperature
low
67
Option change
69
Pwr. Card Temp
70
Illegal FC config
80
Drive initialised
Auto DC
87
Braking
Option
88
detection
93
Dry pump
94
End of curve
95
Broken belt
99
Locked rotor
Flow/pressure
101
info missing
126
Motor Rotating
127
Back EMF too
high
200
Fire Mode
Fire Mode
202
Limits Exceeded
Memory
206
module
Memory
207
module alarm
Table 5.2 Warnings and Alarms
MG03N202
Programming Guide
Warning
Alarm
Trip lock Cause of problem
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Danfoss A/S © 11/2015 All rights reserved.
The user has interrupted the AMA.
Restart the AMA some times, until the AMA is complete.
NOTICE
Repeated runs can heat the motor to a level where the
resistance R
and R
are increased. Usually, however, this
s
r
increased resistance is not critical.
Contact the local Danfoss supplier.
The current is higher than the value in parameter 4-18 Current Limit.
External interlock is activated. To resume normal operation, apply
24 V DC to the terminal programmed for external interlock and reset
the frequency converter. Reset via serial communication, digital I/O, or
[Reset] on the LCP).
The minimum required current for opening the mechanical brake has
not been reached.
The heat sink temperature is measured as 0 °C. This result could
indicate that the temperature sensor is defect. The defect causes the
fan speed to increase to its maximum to cool down the power part or
control card.
The temperature sensor on the power card is either too hot or too
cold.
Power size configuration fault on the power card.
All parameter settings are initialized to default settings.
The frequency converter is auto DC braking.
Torque is below the torque level set for no load, indicating a broken
belt. See parameter group 22-6* Broken Belt Detection.
The frequency converter detected a locked rotor situation. See
parameter 30–22 Locked Rotor Protection and parameter 30–23 Locked
Rotor Detection Time [s].
Flow/pressure information is missing.
High back EMF voltage. Stop the rotor of the PM motor.
Fire mode is activated.
Fire mode has suppressed 1 or more warranty voiding alarms.
5
5
119