3.11.2 Status Word According to FC Profile
(STW) (parameter 8-30 Protocol = FC
profile)
Follower-master
3
3
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
no.:
Illustration 3.21 Status Word
Bit
Bit=0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed≠reference
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Table 3.29 Status Word According to FC Profile
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=0: The frequency converter trips.
Bit 00=1: The frequency converter controls are ready but
the power component does not necessarily receive any
supply (if there is 24 V external supply to controls).
Bit 01, Drive ready
Bit 01=0: The frequency converter is not ready.
Bit 01=1: The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02=0: The frequency converter releases the motor.
Bit 02=1: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=0: The frequency converter is not in fault mode. Bit
03=1: The frequency converter trips. To re-establish
operation, press [Reset].
32
STW
Output freq.
Bit=1
Control ready
Drive ready
Enable
Trip
Error (no trip)
Triplock
Warning
Speed=reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
Danfoss A/S © 11/2015 All rights reserved.
®
VLT
DriveMotor FCP 106/FCM 106
Bit 04, No error/error (no trip)
Bit 04=0: The frequency converter is not in fault mode.
Bit 04=1: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The frequency converter is not in fault mode.
Bit 06=1: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed reference/speed=reference
Bit 08=0: The motor runs but the present speed is different
from the preset speed reference. It might, for example, be
the case when the speed ramps up/down during start/
stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [Off/Reset] is activated on the control unit or [2]
Local in parameter 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09=1: It is possible to control the frequency converter
via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
parameter 4-12 Motor Speed Low Limit [Hz] or
parameter 4-14 Motor Speed High Limit [Hz].
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The frequency converter has a start signal
without coast.
Bit 12, Drive OK/stopped, autostart
Bit 12=0: There is no temporary overtemperature on the
frequency converter.
Bit 12=1: The frequency converter stops because of
overtemperature but the unit does not trip and resumes
operation once the overtemperature normalizes.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the frequency converter's DC
link is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14=0: The motor current is lower than the current limit
selected in parameter 4-18 Current Limit.
Bit 14=1: The current limit in parameter 4-18 Current Limit is
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and
thermal protection are not exceeded 100%.
Bit 15=1: One of the timers exceeds 100%.
MG03N202