Parameters
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for parameter 5–40 Function Relay:
When parameter 0-03 Regional Settings is set to [0] International,
the default value of Relay1 is Alarm, and default value of Relay2
4
4
is Drive Running.
When parameter 0-03 Regional Settings is set to [1] North America,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
[166] Remote ref.
active
[167] Start command
activ
[168] Drive in hand
mode
[169] Drive in auto
mode
[191] Dry Pump
[192] End Of Curve
[193] Sleep Mode
[194] Broken Belt
Function
[196] Fire Mode
[198] Drive Bypass
[235] Check Valve
Ramping
64
®
VLT
DriveMotor FCP 106/FCM 106
Function:
[0] Linked to hand auto at the same time
as the LCP is in [Hand on] mode.
The output is high when
parameter 3-13 Reference Site [1] or Linked
to hand/auto [0] while the LCP is in [Auto
on] mode.
The output is high when there is an
active start command (that is via digital
input bus connection or [Hand on] or
[Auto on], and no stop command is
active.
The output is high when the frequency
converter is in hand on mode (as
indicated by the LED light above [Hand
on].
The output is high when the frequency
converter is in auto on mode (as
indicated by the LED light above [Auto
on].
The frequency converter/system is in
sleep mode. See parameter group 22-4* -
Sleep Mode.
A broken-belt condition is detected.
Enable this function in
parameter 22-60 Broken Belt Function.
The frequency converter is operating in
fire mode. See parameter group 24-0* Fire
mode.
To be used as signal for activating an
external electromechanical bypass,
switching the motor direct on line.
See 24-1* Drive Bypass.
Danfoss A/S © 11/2015 All rights reserved.
5-41 On Delay, Relay
Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
[0.01 - 600
Enter the delay of the relay cut-in time.
*
s]
The relay only cuts in if the condition in
parameter 5-40 Function Relay is uninter-
rupted during the specified time. Select 1
of the available mechanical relays in an
array function. See
parameter 5-40 Function Relay.
Selected
Event
Relay
output
On Delay
P 5-41
Selected
Event
Relay
output
On Delay
P 5-41
Illustration 4.10 On Delay, Relay
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
[0.01 - 600
Enter the delay of the relay cut-out time.
*
s]
Select 1 of the available mechanical relays
in an array function. See
parameter 5-40 Function Relay.
Selected
Event
Relay
output
On Delay
P 5-41
Illustration 4.11 Off Delay, Relay
If the selected event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
O Delay
P 5-42
O Delay
P 5-42
MG03N202