Parameters
4.3.2 2-2* Mechanical Brake
Parameters for setting the speed and current of the
mechanical brake.
2-20 Release Brake Current
Range:
Function:
0 A
[0 - 100
Set the motor current for release of the
*
A]
mechanical brake, when a start condition is
present. The upper limit is specified in
parameter 16–37 Inv. Max. Current.
2-22 Activate Brake Speed [Hz]
Range:
Function:
0 Hz
[0 - 400 Hz] Set the motor frequency for activation of
*
the mechanical brake, when a stop
condition is present.
MG03N202
Programming Guide
Danfoss A/S © 11/2015 All rights reserved.
4
4
51