Programming
Two-finger initialization
Use this method to initialize the frequency converter,
2
2
including reset of communication settings.
1.
Power off the frequency converter.
2.
Press [OK] and [Menu] simultaneously.
3.
Power up the frequency converter while still
pressing the above-mentioned keys for 10 s.
The frequency converter is now reset, except for the
following parameters:
Parameter 0-03 Regional Settings.
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
Parameter group 15-4* Drive identification
parameters
Alarm 80, Drive initialised appears as confirmation that
parameters are initialized. Press [Reset].
14
®
VLT
DriveMotor FCP 106/FCM 106
Danfoss A/S © 11/2015 All rights reserved.