Parameters
4.6.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminal 29 acts as frequency reference
inputs. Set terminal 29 (parameter 5-13 Terminal 29 Digital
Input to [32] Pulse input.
Ref.
(RPM)
High
ref.
value
P 5-53
Low
ref.
value
P 5-52
Low freq.
P 5-50
Illustration 4.12 Pulse Input
5-50 Term. 29 Low Frequency
Range:
Function:
20 Hz
[20 -
Enter the low frequency limit
*
31999 Hz]
corresponding to the low motor shaft
speed (that is low reference value) in
parameter 5-52 Term. 29 Low Ref./Feedb.
Value. Refer to Illustration 4.12.
5-51 Term. 29 High Frequency
Range:
Function:
32000
[21 -
Enter the high frequency limit
Hz
32000 Hz]
corresponding to the high motor shaft
*
speed (that is high reference value) in
parameter 5-53 Term. 29 High Ref./Feedb.
Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0
[-4999 -
Enter the low reference value limit for the
*
4999 ]
motor shaft speed [RPM]. This value is also the
lowest feedback value, see also
parameter 5-13 Terminal 29 Digital Input = [32]
Pulse Input.
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
Size
[-4999 -
Enter the high reference value [RPM]
related
4999 ]
for the motor shaft speed and the high
*
feedback value, see also
parameter 5-13 Terminal 29 Digital Input
= [32] Pulse Input.
MG03N202
Programming Guide
4.6.6 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
0
*
Bit 0–3
Bit 4
Bit 5
Bit 6–23
Bit 24
High freq.
Input
P 5-51
(Hz)
Bit 25
Bit 26–31
Table 4.6 Bit Functions
Danfoss A/S © 11/2015 All rights reserved.
Function:
[0 - 0xFFFFFFFF ] This parameter holds the state of the
digital outputs and relays controlled by
bus.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Reserved
Relay 1 output terminal
Relay 2 output terminal
Reserved
Terminal 42 digital output
Terminal 45 digital output
Reserved
4
4
65