Parameters
6-74 Terminal 45 Output Max Scale
Range:
Function:
Current
(mA)
20
0/4
0%
Analogue
output
Min Scale
par. 6-73
Illustration 4.14 Output Maximum Scale
6-76 Terminal 45 Output Bus Control
Range:
Function:
0
[0 - 16384 ] Holds the level of analog output if controlled
*
by bus.
4.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output terminal 42. Analog outputs are current outputs:
0/4–20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set up as digital output.
6-90 Terminal 42 Mode
Option:
Function:
Set terminal 42 to act as analog output or
as digital output.
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
Function:
Select the function of terminal 42 as an
analog current output. See also
parameter 6–90 Terminal 42 Mode.
[0]
No operation
*
[100] Output frequency 0–100 Hz
[101] Reference
Min
Ref.
[102] Feedback
Min
FB
[103] Motor Current
0–I
max
[106] Power
0–P
nom
[139] Bus Control
0–100%
MG03N202
Programming Guide
Analogue
100%
Variable
Output
for
Max Scale
output
par. 6-74
example:
Power
- Max
Ref.
- Max
FB
Danfoss A/S © 11/2015 All rights reserved.
6-92 Terminal 42 Digital Output
Option:
[0]
No operation
*
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal
warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[32]
Mech brake ctrl
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
Function:
Select the function of
terminal 42 as an analog
current output. See also
parameter 6–90 Terminal 42
Mode. See
parameter 5-40 Function
Relay for description of the
options.
69