Danfoss VLT DriveMotor FCP 106 Programming Manual page 39

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Parameters
0-20 Display Line 1.1 Small
Option:
Function:
[1685]
FC Port CTW 1
Control word (CTW) received from
the Bus Master.
[1686]
FC Port REF 1
Status word (STW) sent to the Bus
Master.
[1690]
Alarm Word
One or more alarms in a hex code
(used for serial communications).
[1691]
Alarm Word 2
One or more alarms in a hex code
(used for serial communications).
[1692]
Warning Word
One or more warnings in a hex code
(used for serial communications).
[1693]
Warning Word 2
One or more warnings in a hex code
(used for serial communications).
[1694]
Ext. Status Word
One or more status conditions in a
hex code (used for serial communi-
cations).
[1695]
Ext. Status Word
One or more status conditions in a
2
hex code (used for serial communi-
cations).
[1697]
Alarm Word 3
[1850]
Sensorless
Readout [unit]
0-21 Display Line 1.2 Small
Select a variable for display in line 1, middle position.
Option:
Function:
[1614]
Motor Current The options are the same as those listed
*
in parameter 0-20 Display Line 1.1 Small.
0-22 Display Line 1.3 Small
Select a variable for display in line 1, right position.
Option:
Function:
[1610]
Power [kW] The options are the same as those listed in
*
parameter 0-20 Display Line 1.1 Small.
0-23 Display Line 2 Large
Select a variable for display in line 2.
Option:
Function:
[1613]
Frequency The options are the same as those listed in
*
parameter 0-20 Display Line 1.1 Small.
0-24 Display Line 3 Large
Select a variable for display in line 3.
MG03N202
Programming Guide
4.1.3 0-3* LCP Custom Readout and Display
Text
It is possible to customize the display elements for various
purposes.
Custom readout
The calculated value to be shown is based on settings in
parameter 0-30 Custom Readout Unit,
parameter 0-31 Custom Readout Min Value (linear only),
parameter 0-32 Custom Readout Max Value,
parameter 4-14 Motor Speed High Limit [Hz], and actual
speed.
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
Illustration 4.1 Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit:
Unit type
Dimensionless
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Power
Table 4.1 Speed Relation
0-30 Custom Readout Unit
Option:
Danfoss A/S © 11/2015 All rights reserved.
0
Speed relation
Linear
Quadratic
Cubic
Function:
Program a value to be shown in the
display of the LCP. The value has a linear,
squared, or cubed relation to speed. This
relation depends on the unit selected (see
Table 4.1). The actual calculated value can
4
4
Motor Speed
Motor Speed
High limit
P 4-14 (Hz)
37