RS485 Installation and Set-...
3.11.3 Bus Speed Reference Value
Speed reference value is transmitted to the frequency
converter in a relative value in %. The value is transmitted
in the form of a 16-bit word; in integers (0–32767) the
value 16384 (4000 hex) corresponds to 100%. Negative
figures are formatted by 2's complement. The actual
output frequency (MAV) is scaled in the same way as the
bus reference.
Master-slave
CTW
Speed reference
Follower-slave
Actual output
STW
frequency
Illustration 3.22 Actual Output Frequency (MAV)
The reference and MAV are scaled as follows:
(0hex)
Par.3-02
Min reference
Illustration 3.23 Reference
-100%
0%
(C000hex)
(0hex)
Reverse
Par.3-03
0
Max reference
Illustration 3.24 MAV when Parameter 1-00 Configuration Mode
is set to [0] Open Loop
-100%
0%
(C000hex)
(0hex)
Reverse
Par.4-14
0
Motor Speed High Limit
Illustration 3.25 MAV when Parameter 1-00 Configuration
Mode is set to [3] Closed Loop
MG03N202
Programming Guide
16bit
0%
100%
(4000hex)
Forward
Par.3-03
Max reference
100%
(4000hex)
Forward
Par.3-03
Max reference
100%
(4000hex)
Forward
Par.4-14
Motor Speed High Limit
Danfoss A/S © 11/2015 All rights reserved.
3
3
33