Parameters
8-42 PCD Write Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs.
The number of PCDs depends on the PPO type.
The values in PCD 3–10 are written to the selected parameters as
data values.
Option:
[11]
[590] Digital & Relay Bus
Control
[12]
[676] Terminal45 Output Bus
Control
[13]
[696] Terminal 42 Output Bus
Control
[14]
[894] Bus Feedback 1
[15]
FC Port CTW
[16]
FC Port REF
8-43 PCD Read Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs.
The number of PCDs depends on the PPO type.
PCD 3–10 hold the real-time data value of the selected
parameters.
Option:
[0]
None
[1]
[1500] Operation Hours
[2]
[1501] Running Hours
[3]
[1502] kWh Counter
[4]
[1600] Control Word
[5]
[1601] Reference [Unit]
[6]
[1602] Reference %
[7]
[1603] Status Word
[8]
[1605] Main Actual Value [%]
[9]
[1609] Custom Readout
[10]
[1610] Power [kW]
[11]
[1611] Power [hp]
[12]
[1612] Motor Voltage
[13]
[1613] Frequency
[14]
[1614] Motor Current
[15]
[1615] Frequency [%]
[16]
[1616] Torque [Nm]
[17]
[1618] Motor Thermal
[18]
[1630] DC Link Voltage
[19]
[1634] Heatsink Temp.
[20]
[1635] Inverter Thermal
[21]
[1638] SL Controller State
[22]
[1650] External Reference
[23]
[1652] Feedback [Unit]
[24]
[1660] Digital Input 18,19,27,33
[25]
[1661] Terminal 53 Switch Setting
[26]
[1662] Analog Input 53(V)
[27]
[1663] Terminal 54 Switch Setting
[28]
[1664] Analog Input 54
[29]
[1665] Analog Output 42 [mA]
[30]
[1671] Relay Output [bin]
[31]
[1672] Counter A
[32]
[1673] Counter B
MG03N202
Programming Guide
8-43 PCD Read Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs.
The number of PCDs depends on the PPO type.
PCD 3–10 hold the real-time data value of the selected
parameters.
Function:
Option:
[33]
[34]
[35]
[36]
4.8.5 8-5* Digital/Bus
Parameters for configuring the control word digital/bus
merging.
8-50 Coasting Select
Option:
Function:
[0]
Digital
input
[1]
Bus
[2]
Logic
AND
[3]
Logic OR Activates coast via the serial communication port
*
8-51 Quick Stop Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic
AND
[3]
Logic OR Activates quick stop via the serial communi-
*
Danfoss A/S © 11/2015 All rights reserved.
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
[1850] Sensorless Readout [Unit]
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
Activates coast via a digital input.
Activates coast via the serial communication
port.
Activates coast via the fieldbus/serial communi-
cation port, and via 1 of the digital inputs.
or via 1 of the digital inputs.
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the Quick Stop function via the
terminals (digital input) and/or via the bus.
Activates quick stop via a digital input.
Activates quick stop via the serial communi-
cation port.
Activates quick stop via the serial communi-
cation port, and via 1 of the digital inputs.
cation port or via 1 of the digital inputs.
Function:
4
4
73