Parameters
5-34 On Delay, Digital Output
Range:
0.01 s
[0 - 600 s] Enter the delay time before the digital
*
5-35 Off Delay, Digital Output
4
4
Range:
0.01 s
[0 - 600 s] Enter the delay time before the digital
*
4.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for parameter 5–40 Function Relay:
When parameter 0-03 Regional Settings is set to [0] International,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When parameter 0-03 Regional Settings is set to [1] North America,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/
remote control
[4]
Standby / no
warning
[5]
Drive running
[6]
Running / no
warning
[7]
Run in
range/no
warning
[8]
Run on ref/no
warning
62
®
VLT
DriveMotor FCP 106/FCM 106
Function:
output is switched on. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
Function:
output is switched off. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
Function:
Default for both relays.
The control board receives supply voltage.
The frequency converter is ready for
operation and applies supply signal on
control board.
The frequency converter is ready for
operation in Auto On mode.
The frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
The motor runs.
The motor runs, and no warnings are
present.
The motor runs within programmed
current ranges, see
parameter 4-50 Warning Current Low and
parameter 4-51 Warning Current High. No
warnings are present.
The motor runs at reference speed and
with no warnings.
Danfoss A/S © 11/2015 All rights reserved.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for parameter 5–40 Function Relay:
When parameter 0-03 Regional Settings is set to [0] International,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When parameter 0-03 Regional Settings is set to [1] North America,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
Function:
[9]
Alarm
An alarm activates output.
[10]
Alarm or
An alarm or warning activates output.
warning
[12]
Out of current
The motor current is outside the range
range
set in parameter 4-50 Warning Current Low
and parameter 4-51 Warning Current High.
[13]
Below current,
The motor current is lower than set in
low
parameter 4-50 Warning Current Low.
[14]
Above current,
The motor current is higher than set in
high
parameter 4-51 Warning Current High.
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below
feedback, low
[20]
Above
feedback, high
[21]
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in motor,
frequency converter, or thermistor.
[22]
Ready, no
The frequency converter is ready for
thermal
operation and no overtemperature
warning
warning is present.
[23]
Remote, ready,
The frequency converter is ready for
no thermal
operation in Auto mode, and no overtem-
warning
perature warning is present.
[24]
Ready, Voltage
The frequency converter is ready for
OK
operation, and mains voltage is within
specified voltage range.
[25]
Reverse
The motor runs/is ready to run clockwise
when logic = 0 and counterclockwise
when logic = 1. Output changes when
reversing signal is applied.
[26]
Bus OK
Active communication (no timeout) via
serial communication port.
[32]
Mech brake ctrl
[35]
External
See digital input.
Interlock