Parameters
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast.
NOTICE
Can cause PWM when coasted.
[0]
Off This function is not active.
[1]
On
This function is active.
*
4.1.2 0-1* Define and Set-up Operations
A complete set of all parameters controlling the frequency
converter is called a set-up. The frequency converter
contains 2 set-ups: Set-up 1 and set-up 2. Furthermore, a
fixed set of factory settings can be copied into 1 or both
set-ups.
Some of the advantages of having more than 1 set-up in
the frequency converter are:
Run the motor in 1 set-up (active set-up) while
updating parameters in another set-up (edit set-
up).
Connect the 2 motors (1 at a time) to the
frequency converter. Motor data for the 2 motors
can be placed in the 2 set-ups.
Rapidly change settings of the frequency
converter and/or the motor while the motor runs.
For example, ramp time or preset references via
bus or digital inputs.
The active set-up can be set as multi set-up, where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
To copy set-up 1 to set-up 2, or copy set-up 2 to set-up 1,
use parameter 0-51 Set-up Copy. To avoid conflicting
settings of the same parameter within 2 different set-ups,
link the set-ups using parameter 0-12 Link Setups. Stop the
frequency converter before switching between set-ups
where parameters marked not changeable during operation
have different values.
Parameters that are not changeable during operation are
marked false in chapter 6 Parameter Lists.
0-10 Active Set-up
Option:
Function:
Select the set-up in which the frequency
converter operates.
[1]
Set-up 1
Set-up 1 is active.
*
[2]
Set-up 2
Set-up 2 is active.
[9]
Multi Set-
Used for remote set-up selections via digital
up
inputs and the serial communication port. This
MG03N202
Programming Guide
0-10 Active Set-up
Option:
0-11 Programming Set-up
Option:
[1]
Set-up 1
[2]
Set-up 2
[9]
Active Set-up Edit parameters in the set-up selected via
*
0-12 Link Setups
Option:
[0]
Not
linked
[20]
Linked
*
0-20 Display Line 1.1 Small
Option:
[0]
[37]
[38]
[39]
[953]
[1501]
[1502]
[1600]
Danfoss A/S © 11/2015 All rights reserved.
Function:
set-up uses the settings from
parameter 0-12 Link Setups.
Function:
The number of the set-up being edited is
shown in the LCP, flashing.
Edit set-up 1
Edit set-up 2
digital I/Os.
Function:
If the set-ups are not linked, a change between
them is not possible while the motor runs.
When selecting a different set-up for operation,
the set-up change does not occur until the
motor is coasted.
Copies not changeable during operation
parameters from 1 set-up to the other. It is
possible to switch set-ups while the motor runs.
Function:
Select a variable for display in line 1,
left position.
No display value selected.
Display Text 1
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
Display Text 2
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
Display Text 3
Enables an individual text string to be
written, for showing in the LCP or to
be read via serial communication.
Profibus Warning
Shows PROFIBUS communication
Word
warnings.
Running Hours
View the number of running hours of
the motor.
kWh Counter
View the mains power consumption
in kWh.
Control Word
View the Control Word sent from the
frequency converter via the serial
communication port in hex code.
4