Parameters
0-20 Display Line 1.1 Small
Option:
[1601]
Reference [Unit]
[1602]
Reference [%]
*
4
4
[1603]
Status Word
[1605]
Main Actual
Value [%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor current
[1615]
Frequency [%]
[1616]
Torque [Nm]
[1618]
Motor Thermal
[1622]
Torque [%]
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link Voltage
[1634]
Heatsink Temp.
[1635]
Inverter Thermal
36
®
VLT
DriveMotor FCP 106/FCM 106
Function:
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow down) in selected unit.
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow down) in percent.
Present status word.
View the 2-byte word sent with the
status word to the bus master
reporting the main actual value.
View the user-defined readouts as
defined in parameter 0-30 Custom
Readout Unit, parameter 0-31 Custom
Readout Min Value, and
parameter 0-32 Custom Readout Max
Value.
Actual power consumed by the motor
in kW.
Actual power consumed by the motor
in hp.
Voltage supplied to the motor.
Motor frequency, that is, the output
frequency from the frequency
converter in Hz.
Phase current of the motor measured
as effective value.
Motor frequency, that is, the output
frequency from the frequency
converter in percent.
Present motor load as a percentage
of the rated motor torque.
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
Shows the actual torque produced, in
percentage.
DC-link voltage in the frequency
converter.
Present heat sink temperature of the
frequency converter. The cut-out limit
is 95 ± 5 °C; cutting back in occurs at
70 ± 5 °C.
Percentage load of the inverters.
Danfoss A/S © 11/2015 All rights reserved.
0-20 Display Line 1.1 Small
Option:
Function:
[1636]
Inv. Nom. Current Nominal current of the frequency
converter.
[1637]
Inv. Max. Current
Maximum current of the frequency
converter.
[1638]
SL Controller
State of the event executed by the
State
control.
[1639]
Control Card
Temperature of the control card.
Temp.
[1650]
External
Sum of the external reference as a
Reference
percentage, that is, the sum of
analog/pulse/bus.
[1652]
Feedback[Unit]
Reference value from programmed
digital inputs.
[1660]
Digital Input
Shows the status of the digital inputs.
Signal low = 0; Signal high = 1.
Regarding order, see
parameter 16-60 Digital Input. Bit 0 is
at the extreme right.
[1661]
Terminal 53
Setting of input terminal 53. Current
Setting
= 0; Voltage = 1.
[1662]
Analog Input
Actual value at input 53 either as a
AI53
reference or protection value.
[1663]
Terminal 54
Setting of input terminal 54. Current
Setting
= 0; Voltage = 1.
[1664]
Analog Input
Actual value at input 54 either as
AI54
reference or protection value.
[1665]
Analog Output
Actual value at output 42 in mA. Use
AO42 [mA]
parameter 6-50 Terminal 42 Output to
select the variable to be represented
by output 42.
[1666]
Digital Output
Binary value of all digital outputs.
[1667]
Pulse Input #29
Actual value of the frequency applied
[Hz]
at terminal 29 as a pulse input.
[1671]
Relay Output
View the setting of all relays.
[bin]
[1672]
Counter A
View the present value of Counter A.
[1673]
Counter B
View the present value of Counter B.
[1679]
Analog Output
AO45
[1680]
Fieldbus CTW 1
Control word (CTW) received from
the Bus Master.
[1682]
Fieldbus REF 1
Main reference value sent with
control word via the serial communi-
cations network for example, from
the BMS, PLC, or other master
controller.
[1684]
Comm. Option
Extended fieldbus communication
STW
option status word.
MG03N202