Parameters
14-12 Function at Mains Imbalance
Option:
4
4
[0]
Trip
*
[1]
Warning Issues a warning.
[2]
Disabled No action.
4.11.3 14-2* Trip Reset
14-20 Reset Mode
Option:
[0]
Manual reset
*
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
90
VLT
Function:
NOTICE
Selecting this option may reduce the life
time of the frequency converter.
Operation under severe mains imbalance
conditions reduces the lifetime of the motor. If
the motor is operated continuously near nominal
load, conditions are considered severe.
When a severe mains imbalance is detected,
select 1 of the available functions.
Trips the frequency converter.
Function:
NOTICE
Automatic reset is also active for
resetting theSafe Torque Off
function.
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
Select [0] Manual reset, to perform a
reset via [Reset] or via the digital
inputs.
Select [1]-[12] Automatic reset x 1...
x20 to perform between 1 and 20
automatic resets after tripping.
Select [13] Infinite Automatic Reset for
continuous resetting after tripping.
Danfoss A/S © 11/2015 All rights reserved.
®
DriveMotor FCP 106/FCM 106
14-21 Automatic Restart Time
Range:
10 s
[0 - 600
*
s]
14-22 Operation Mode
Option:
[0]
Normal
operation
*
[2]
Initiali-
sation
14-27 Action At Inverter Fault
Select how the frequency converter acts in the case of
overvoltage, overcurrent, short circuit, or grounding errors.
Option:
[0]
[1]
*
14-28 Production Settings
Option:
[0]
No action
*
[1]
Service reset
[3]
Software Reset
14-29 Service Code
Range:
0
[0 - 0x7FFFFFFF ]
*
4.11.4 14-3* Current Limit Control
The frequency converter features an integral current limit
controller which is activated when the motor current, and
thus the torque, is higher than the torque limits set in
parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
When the current limit is reached during motor operation
or regenerative operation, the frequency converter tries to
reduce torque below the preset torque limits as quickly as
possible without losing control of the motor.
While the current control is active, the frequency converter
can only be stopped by setting a digital input to [2] Coast
inverse or [3]Coast and reset inv. Any signal on terminals 18
Function:
To start of the automatic reset function, enter
the time interval from trip . This parameter is
active when parameter 14-20 Reset Mode is set
to [1] - [13] Automatic reset.
Function:
To reset all parameter values to default, select
[2] initialization.
Select [0] Normal operation for normal
operation of the frequency converter with the
motor in the selected application.
Select [2] initialization to reset all parameter
values to default settings, excluding bus
communication parameters, parameter groups
15-0* Operating Data and 15-3* Alarm Log. The
frequency converter is reset during the next
power-up.
Parameter 14-22 Operation Mode also reverts to
the default setting [0] Normal operation.
Function:
Trip
Warning
Function:
Function:
Service use only.
MG03N202